WARNING: An open bottom stationary engine generator set must be installed over noncombustible materials and shall be located such that it prevents combustible materials from accumulating under the generator set.

Several other factors should be carefully evaluated when selecting a location for installation:

1.For effective cooling and maintenance, the system should be mounted on a flat, smooth, noncombustible level surface. A concrete pad is ideal and provides a secure installation.

2.Installation should prevent water levels from reaching the generator. Drainage must be adequate to keep concrete pad free from standing water.

3.Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If these items pose a problem, consider building a small fence or other break to protect the unit from accumulation of debris.

4.Installation should place the generator as close as possible to the fuel supply and transfer switch.

5.At least twenty-four (24) inches clearance must be provided on all sides for air flow.

6.Access must be provided to allow the enclosure covers to be opened or removed for service and maintenance.

7.Maximum Ambient temperature is 122°F (50°C).

 

Figure 3‐2 Generator Mounting

 

Fuel Stub Up

 

 

GLC125 ONLY

 

 

Large Exhaust Area

 

B1

For all models with enclosure

 

 

 

B

 

Fuel Stub Up

Electrical Stub Up

A3

 

 

A1

A2

A2

 

F1

 

A

F2

 

A

 

Table 3‐2 Mounting Dimensions

Generator

A

A

A

A1

A2

A3

B

B1

F1

F2

 

(Open)

(Weather.)

(Sound)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLC10-25

60.25

72.0

72.0

4.0

26.1

11.75

31.5

30.5

17.6

34.2

GLC30-45

78.0

78.0

108.0

6.0

33.0

30.0

44.0

42.5

21

58

GLC60-65

88.0

88.0

118.0

6.0

38.0

30.0

44.0

42.5

23

63

GLC80-105

88.0

88.0

118.0

6.0

38.0

30.0

44.0

42.5

27

68

 

 Add 11.75 in

for Weather & Sound Attenuated enclosures.

 

 

 

 

Table 3‐3 Stub Up Detail

 

 

 

 

 

 

Generator

Stub Up Area

 

 

Fuel Connection (NG or LP Vapor)

Electrical

 

Fuel

 

 

 

 

 

 

 

GLC10-25

6.25” x 5”

 

5” x 18”

 

3/ ” NPT, C/L is 3” above base bottom.

 

 

 

 

 

4

 

GLC30-45

15” x 6”

 

18”x 6”

 

3/ ” NPT, C/L is 12” above base bottom.

 

 

 

 

 

4

 

GLC60-65

21” x 6”

 

20” x 6”

 

1-

1/ ” NPT, C/L is 12” above base bottom.

 

 

 

 

 

 

4

GLC80-105

16” x 6”

 

21” x 6”

 

1-

1/ ” NPT, C/L is 12” above base bottom.

 

 

 

 

 

 

4

3‐2 Receiving & Installation