Baldor GLC60, GLC105, GLC45, GLC20, GLC65, GLC30 Voltage Calibration Procedure, Zero Calibration

Models: GLC40 GLC25 GLC15 GLC100 GLC30 GLC65 GLC20 GLC45 GLC105 GLC60 GLC10

1 114
Download 114 pages 7.44 Kb
Page 67
Image 67

Digital Fault Menu Loop The controller's digital fault settings are described as follows:

Caution: The Digital Fault Label selection must agree with the external control wiring prior to energizing the controller. Failure to do so may cause severe equipment damage.

Digital Fault Label

Select the desired fault label, these are stored in non-volatile memory.

 

 

Air Damper Tripped

High Oil Temp

Bat Charger Input Fail

High Winding Temp

 

Bat Chrg Trouble

Low Coolant Level

Breaker Tripped

Low Engine Temp

 

DC Fail

Low Fuel Level

Failed To Sync

Low Fuel Press

 

Gen Breaker Open

Low Oil Level

Ground Fault

Low Oil Pressure

 

High Bearing Temp

Remote Emerg.stop

High Cooler Vibration

Reverse Power

 

High Engine Temp

Basin Rupture

High Engine Vibration

ATS In Bypass

 

High Fuel Level

Fuel Leak

High Oil Level

Low Fuel Press

 

No Load Test

Bat Charger Fail

*Highintkmanftemp

Vent Damper Fail

 

High Fuel Level

Fail To Sync

“Blank” (i.e. no text for unused inputs)

Action

Allows a fault to be either an Alarm fault or a Shutdown fault.

 

 

 

Note: Any activated alarm or shutdown fault will energize the “Common fail” fault and sound the alarm horn.

Alarm Latch

If an fault was set as an Alarm, it may be selected as a “Latching” alarm or “Non-latching” alarm. A Latching alarm is not

 

cleared until a reset command clears it.

 

 

 

Note: This value only appears if alarm faults are programmed. Shutdown faults are automatically set as latching.

Polarity

Allows the digital fault circuit to be set for Open to Fail or Close to Fail sensing contacts.

 

Bypass On Start Delay

Allows the alarm or shutdown fault to be disabled until after the bypass timer has expired. Faults that are not delayed are

 

enabled at all times (i.e. engine running or stopped).

 

 

Transient Delay Times

Allows the selected fault to be disabled until the delay period has expired. Delay times are 0.0 to 999.9 seconds.

Idle Control Digital Input Programming When a digital input is set to Idle function, these settings must be programmed to ensure correct operation:

Action

Alarm

Alarm Latch

No

Polarity

Close

Bypass On Start

No

Transient Time

0.1

Note: The corresponding digital output must also be programmed for IDLE to enable correct operation.

No Load Test Control Digital Input Programming

The No Load Test digital input feature is typically used in an AMF application where it is required to do an automatic timed No Load Test of the engine/generator set. A contact from an external exercise clock timer is required to be connected to the digital input circuit which is programmed for “No Load Test”. When a digital input is programmed as No Load Test, these settings must be programmed to ensure correct operation:

Action

Alarm

Alarm Latch

No

Polarity

Close Or Open (dependent on external circuit used)

Bypass On Start

No

Transient Time

0.1

Calibration Menu Loop AC Voltage, AC current and battery voltage analog circuits are factory calibrated and should not require field calibration. If field calibration is required, refer to the calibration procedure.

Voltage Sensing Calibration (Phase To Phase or Phase To Neutral)

VOLTS AB ZERO

99 600V

Displays the generator phase voltages to be calibrated. Displays the type of calibration function, either ZERO or SPAN.

Displays the calibration correction factor number (0-255) used to obtain the correct voltage reading.

Note: To correctly calibrate any of the voltage sensors, the ZERO function must be calibrated before the SPAN function. Displays the actual voltage measurement that will be the same value as shown on the MEC 2 display menus for generator supply. This voltage reading may be calibrated higher or lower by changing the correction factor number.

Voltage Calibration Procedure

Note:

Zero Calibration must be completed before Span Calibration.

Zero Calibration

Connect an external AC voltmeter of adequate voltage range and accuracy to the MEC 2 controller terminals associated

 

with the voltage phases to be calibrated. With the generator stopped, confirm there is Zero volts on the phases to be

 

calibrated. In the programming mode, scroll to each of the desired generator supply voltage phases (i.e. phase to phase

 

or phase to neutral) with the ZERO function selected. Use the INCREMENT or DECREMENT push-buttons to adjust the

 

correction factor number to obtain zero volts on the right hand side of the display as confirmed with the external

 

voltmeter. The factory default correction factor is 127. Increasing this will raise the displayed value, conversely

 

decreasing this value will decrease the displayed value. Note: Adjusting the ZERO function with voltage applied will result

 

in non-linear voltage readings.

 

With the correct voltage displayed, press the ENTER push-button to accept the correction factor number. Record the

 

correction factor number on the programming sheet for future reference. Repeat this procedure for all remaining phases.

MN2408

Operation 4‐27

Page 67
Image 67
Baldor GLC60, GLC105, GLC45, GLC20, GLC65, GLC30, GLC100, GLC15, GLC25, GLC40 Voltage Calibration Procedure, Zero Calibration