Table 4‐15 Engine Setpoints

 

 

 

 

 

 

 

 

 

 

Start RPM

 

 

“Firing” speed when iL controller stops cranking (starter goes OFF).

 

 

 

Step: 1% of nominal RPM; Range: 5 - 50 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Starting POil

 

 

When reached controller stops cranking (starter goes OFF).

 

 

 

Step: 0,1 psi; Range: -100 - 10000

 

 

 

Note: There are three conditions for stop cranking: Starting RPM,

 

 

 

 

 

StartingPOil and D+ (when enabled). Starter goes off when any

 

 

 

 

 

of these conditions is valid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Prestart time

 

 

Time of closing of the PRE-START output prior to the engine start.

 

 

 

Set to zero if you want to leave the output PRE-START open.

 

 

 

Step: 1s; Range: 0 - 600 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MaxCrank time

 

 

Maximum time limit of cranking.

Step: 1s; Range: 1 - 60 s

CrnkFail pause

 

 

Pause between crank attempts. Step: 1s; Range: 5 - 60 s

Crank attemps

 

 

Max number of crank attempts. Step: 1; Range: 1 - 10

Idle time

 

 

Idle time delay starts when RPM exceeds Start RPM . Start fail is detected

 

 

 

when during Idle state RPM decreases below 2.

 

 

 

During the Idle time timer running the binary output IDLE/NOMINAL is

 

 

 

opened, when it elapses the IDLE/NOMINAL output closes.

 

 

 

Binary output IDLE/NOMINAL opens during Cooling period again.

 

 

 

Step: 1 s; Range: 0 - 600 s

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: If the IDLE function not supported on the governor, set the Idle time

 

 

 

 

 

nevertheless to minimum 5s to avoid Underspeed possibly

 

 

 

 

 

caused by instability of the engine short after start.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GCB CloseDelay

 

 

GCB can be closed earliest GCB CloseDelay after Stabil time when all

 

 

 

electric values are in overunder voltage and over-under frequency limits.

 

 

 

Step: 1 s; Range: 0 - 300 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stabil time

 

 

Generator Nominal voltage is detected during genset start after starter is

 

 

 

switched off and Idle time elapses. Electric generator protections are

 

 

 

active since detection. Step: 1 s; Range: 0 - 300 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MinStpValvTime

 

 

Binary output Stop solenoid closes when stop sequence begins and

 

 

 

closes at least for MinStpValvTime. Example MinStpValvTime = 20 sec.

 

 

 

a) When engine stops (RPM=0) in 10 seconds, Binary output Stop

 

 

 

solenoid still stays closed for 10 sec.

 

 

 

b) When engine stops in 30 seconds, Binary output Stop solenoid opens

 

 

 

10 seconds after RPM=0 and Vg =0 and Oil pressure = 0. Those 10 sec is

 

 

 

fix time for safe stop. Step: 1s; Range: 0 - 180 s

 

 

 

Note: Stop of engine is detected when all following conditions are met:

 

 

 

RPM =0, Oil pressure < StartingPOil and Generator voltage < 10 VAC.

 

 

 

Stop fail is detected when is difference between those conditions, e.g

 

 

 

RPM=O and Generator voltage > 10V.

 

Start RPM

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM = 2

 

 

 

 

 

 

 

 

 

 

Idle Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B O S tarter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BO IDLERA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Idle tim e

 

M in stab tim e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric protections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

activ e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Fail

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stabil Time

MN2408

Operation 4‐7

Page 47
Image 47
Baldor GLC45, GLC60, GLC105, GLC20, GLC65, GLC30, GLC100, GLC15, GLC25, GLC40 manual ‐15 Engine Setpoints