Baldor GLC40 Operator Control Panel Continued, Manual Start/Stop, Automatic Start/Stop, Auto LED

Models: GLC40 GLC25 GLC15 GLC100 GLC30 GLC65 GLC20 GLC45 GLC105 GLC60 GLC10

1 114
Download 114 pages 7.44 Kb
Page 54
Image 54

Operator Control Panel Continued

Auto Switch -

When pushed, initiates automatic operation of the engine (generator set). Starting and stopping of the engine is controlled by a

 

remote contact (transfer switch). When the remote start signal is removed the engine will continue to run for the cool down period

 

(if selected) then stop. Pushing the Off switch will stop the engine immediately, even if the cool down period is not complete.

Auto LED-

On when the Auto Switch is used to start automatic operation.

Load Test Switch -

When pushed, initiates a load test of the generator set with the associated transfer switch. Only operative for AMF connections or

 

if one of the programmable output contacts is configured for “ATS Test” and the remote transfer switch has remote testing circuitry.

 

When pushed, a signal is issued to the remote transfer switch to permit an automatic engine start and load transfer. Once initiated,

 

the engine will receive a start signal from the transfer switch and upon the generator reaching nominal voltage and frequency

 

levels, a load transfer will be initiated. The generator set will remain running at load until a different operating mode is selected or

 

the generator set develops an alarm or shutdown fault condition.

Load Test LED -

On when the load test of the generator set is active.

Special Function Switches Silence

Horn Silence. Press both “Exit and Decrement” at the same time.

 

Lamp Test

This will silence the audible alarm horn without resetting the fail condition.

 

Press both “Decrement and Increment” at the same time.

 

 

Causes the LED's and LCD display to illuminate for approximately 2 seconds then return to their original status.

 

Note:

The emergency stop LED is not affected by this test.

 

Reset

Fault Reset. Press both “Increment and Enter” at the same time.

 

 

Resets the controller when in a shutdown mode.

 

Note:

To reset after a fault, the engine must come to a complete stop and the controller's “OFF” switch must be pressed.

Voltage Adjust -

Increase or Decrease the Generator output voltage (displayed on VOLTAGE meter)

Operating Procedures The engine-generator controller is designed to start and stop an engine from either a local (“Manual”) or remote (“Automatic”) modes. When a start command is issued, the controller issues a run and crank output signal. The controller then monitors engine speed and when crank disconnect speed is reached, the crank signal is terminated. While the engine accelerates to normal speed, the controller continuously monitors the engines speed signal. Should the engine speed exceed the maximum predetermined setpoint, the overspeed shutdown fault circuit will activate, terminating the run signal.

In addition to overspeed shutdown, the engine controller also monitors many other engine protection circuits and should they be activated, the engine will be stopped and/or alarm initiated. The engine will automatically stop for any shutdown condition, or when the remote and/or local start signal is removed. The engine controller operation includes time delay circuits for normal operating conditions such as start delays, cool down and cranking periods.

Manual Start/Stop

To manually Start the Gen-Set, push the “RUN” push-button. The following happens:

1.When the “RUN” push-button is pressed, an ENGINE START DELAY timer is initiated. (The start sequence will not be initiated if any shutdown fault condition is present.)

2.When the engine start delay time expires, an engine RUN and CRANK output signal will be initiated. (The RUN output may be programmed to only energize when a start signal is initiated and an engine speed signal is detected.)

3.When the engine starts and begins to accelerate to nominal speed, the controllers speed sensor will terminate the CRANK output when engine speed reaches approximately 20% speed (i.e. CRANK DISCONNECT speed setpoint). Immediately upon reaching crank disconnect speed, the controller will initiate the BYPASS DELAY time delay function. After the BYPASS DELAY time period (typically 10 seconds) all fault circuits programmed as BYPASS DELAY=YES are active. (All fault circuits programmed as BYPASS DELAY=NO are continuously armed irrespective of any operation sequence.)

To manually Stop the Gen-Set, push the “OFF” push-button. The controllers RUN output will be immediately terminated which will initiate the engine stop sequence.

Automatic Start/Stop

To setup the generator for automatic operation, pressing the “AUTO” push-button.

The following happens:

1.The engine will automatically start upon activation of the remote start contact input. The remote device initiates a start sequence upon contact closure.

2.When the remote start signal is activated, the engine will start as per the sequence of operation described for the manual start sequence.

3.The automatic stop sequence will be initiated by removal of the remote start signal.

4.When the start signal is removed, a cool down delay function will be initiated.

4‐14 Operation

MN2408

Page 54
Image 54
Baldor GLC40 Operator Control Panel Continued, Manual Start/Stop, Automatic Start/Stop, Auto Switch, Auto LED, Lamp Test