Digital Engine Controller Description EM0046A21 (MRS17) Continued

Table 4‐9 Manual Mode Sequence Description

Menu

Status

Condition of Transition

Action 

Next State

 

 

Start request

PRESTART on,

PRESTART

 

 

 

Prestart time counter started

 

 

Ready

 

 

 

 

RPM > 2 or Oil pressure detected or

 

Stop (Stop fail)

 

 

Gen voltage > 10V

 

 

 

 

 

 

 

 

 

OFF mode selected or Shut down alarm active

 

Not Ready

 

Not Ready

RPM < 2, Oil pressure not detected, Vgen < 10V,

 

Ready

 

 

no shutdown alarm active, other than OFF mode

 

 

 

 

selected

 

 

 

 

 

 

 

 

Prestart

Prestart time elapsed

STARTER on, FUEL SOLENOID on,

Cranking

 

 

 

MaxCrank time counter started

 

 

 

 

 

 

 

 

RPM> Start RPM

STARTER off, PRESTART off

Starting

 

 

D+ input activated or oil pressure detected or

STARTER off, PRESTART off

Cranking

 

 

Gen voltage > 25% Vgnom

 

 

 

Cranking

 

 

 

 

MaxCrank time elapsed, 1st attempt

STARTER off, FUEL SOLENOID off,

Crank pause

 

 

 

STOP SOLENOID on,

 

 

 

 

CrankFail pause timer started

 

 

 

 

 

 

Main

 

MaxCrank time elapsed, last attempt

STARTER off, PRESTART off

Shutdown (Start fail)

Crank Pause

CrankFail pause elapsed

STARTER on, FUEL SOLENOID on,

Cranking

Measurement

 

 

STOP SOLENOID off,

 

 

 

 

 

 

 

 

MaxCrank time counter started

 

 

 

 

 

 

 

Starting

30% Nominal speed reached

READY TO LOAD on,

Running

 

 

 

MaxStabTime counter started

 

 

 

 

 

 

 

 

Stop request

READY TO LOAD off,

Cooling

 

Running

 

Cooling time timer started

 

 

 

 

 

 

RPM = 0 or any other shutdown condition

READY TO LOAD off,

Shutdown

 

 

 

 

 

FUEL SOLENOID off

 

 

 

 

 

 

 

Loaded

RPM = 0 or any other shutdown condition

FUEL SOLENOID off, STOP SOLENOID

Shutdown

 

 

on, READY TO LOAD off

 

 

 

 

 

 

 

 

 

 

 

 

Cooling time elapsed

FUEL SOLENOID off,

Stop

 

 

 

STOP SOLENOID on

 

 

Cooling

 

 

 

 

RPM = 0 or any other shutdown condition

FUEL SOLENOID off,

Shutdown

 

 

 

STOP SOLENOID on

 

 

 

 

 

 

 

 

Start request

READY TO LOAD on

Running

 

Stop

RPM = 0, Oil pressure not detected, Vgen < 10V

 

Ready

 

60 sec. Elapsed

 

Stop (Stop fail)

 

 

 

Some output conditions are optional and may require additional programming of field connection. See appropriate wiring diagram.

Adjustment Menu

The adjustment menu, Figure 4‐10 allows setting engine and generator values such as Passwords, Pre-Start Time, Crank Time, Cool Down Time, Alarm Conditions and values, Shutdown Conditions and values, power transfer settings, etc.

Figure 4‐10 Adjustment Menu

>ENGINE BASIC ENGINE PROT GEN BASIC GEN PROTECT

Use Y and B to move the cursor to the desired parameter. Press ENTER to select the parameter group.

Press PAGE to move to the next page of menu items.

Alarm List

Shows the active alarms and warnings. Press fault reset to clear the list.

ECU Alarm List

Shows the active ECU (engine control unit) fault codes. Press ENTER + fault reset to clear the list.

MN2408

Operation 4‐3

Page 43
Image 43
Baldor GLC40, GLC10, GLC60 Adjustment Menu, ECU Alarm List, Menu Status Condition of Transition Action  Next State