Display Modes The controller is in the display mode at all times except when in the programming mode. The display screens and menus may be selected by pressing the Enter or Exit keys to access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or Programming Menus. The LCD display shows the status of the generator output:

Operating Status The controller will power-up into an Emergency Stop failure mode, preventing possible engine operation. The controller must be manually reset before normal operation can be established. To reset the Emergency Stop condition, press the “OFF” push-button first, then press both “INCREMENT” and “ENTER” push-buttons simultaneously. The controller will then reset, if a remote emergency stop condition is not activated. The Utility Ready to Load programmable output will energize if the remote start contact is open. The Main LCD Display will be shown.

Action

Description

 

 

Display

 

 

Comments

 

 

 

 

 

 

 

 

Apply Power and

Main LCD Display.

 

 

 

 

 

 

Vavg

Aavg

Freq

 

 

Reset faults.

 

 

000

000

000

 

 

Press Enter key

Show Operating Status screens

 

 

 

 

 

Controller is in “Auto” position and there

 

 

 

 

 

 

UNIT READY

 

 

 

 

 

 

 

 

are no active faults.

Press or key

Scroll to next.

 

 

 

 

 

Controller is in “OFF” position from the

 

 

 

 

 

SWITCH IN OFF

 

 

 

 

 

 

 

front panel keypad push-button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press or key

Scroll to next.

 

 

 

 

 

Engine is running and all conditions are

UNIT RUNNING

 

 

 

 

 

 

 

normal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press or key

Scroll to next.

 

 

 

 

 

A shutdown fault is active. The specific

UNIT SHUTDOWN

 

 

 

 

 

fault will be automatically displayed.

Press or key

Scroll to next.

 

 

 

 

 

One or more faults are active. The

 

 

 

 

 

UNIT ALARM

 

 

 

 

 

 

 

display will automatically scroll through

 

 

 

 

 

 

 

all active faults at a two second rate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault Display The fault display menu is automatically displayed when an alarm or shutdown fault is activated. The specific alarm or shutdown fault label will be displayed and if multiple alarm conditions are present, the display will automatically scroll through all active faults.