Page 55
Image 55

5.When the cool down time delay period expires (typically 5 minutes), the controllers RUN output will be immediately terminated which will initiate the engine to stop.

Automatic Fault Shutdown

When a fault circuit is programmed as a SHUTDOWN, the engine will immediately stop when the fault is activated. A specific shutdown fault can be programmed with a definite time transient delay period that must expire before the shutdown is activated. The stop sequence will cause the controllers RUN output to be immediately terminated which will cause the engine to stop. This will prevent subsequent operation of the generator set. The Run/Stop/Auto selector switch on the operator control panel must be momentarily placed in the “Stop” position to reset the fault.

Automatic Mains Failure (AMF)

Figure 4‐14 Auto Mains Failure (AMF) Connections

Transfer

Switch

MN2408

Operation 4‐15

Page 55
Image 55
Baldor GLC10 Automatic Fault Shutdown, Automatic Mains Failure AMF, ‐14 Auto Mains Failure AMF Connections Transfer Switch