Secure the Generator
Six (eight for the GLC125) mounting bolts in the base frame secure the generator to the shipping pallet. Remove these bolts, lift the generator and remove the shipping pallet. Secure the generator to the concrete pad using 3/8″ anchor hardware (not provided) in the base frame mounting holes. See Figure 3‐2. Anchor bolts must be long enough to extend through the generator mounting frame.
Engine Cooling A sufficient flow of clean, cool air is required for combustion and to dissipate the heat produced by the engine. Approximately 60% of the heat value of the fuel used is given off as heat (cooling air and exhaust).
The air that will cool the engine must be brought in from outside the building. A sufficient
Note: The exhaust fan must not be located where it could easily become blocked by leaves, snow, water, debris, etc.
It is recommended that the cool air intake have at least three (3) times the
The exhaust fan must be connected to the AC power terminals of the generator set so that when the generator set starts it will provide immediate cooling air flow. The fan will operate until the generator set stops. To test the ventilation system, do the following:
Ventilation Test
1.Place a thermometer as close to the cool air intake of the engine's blower housing as you can without allowing the thermometer to touch any material surface.
2.Place another thermometer outside of the building or compartment in the open air (Keep the thermometer out of direct sunlight or any other heat sources).
3.Run the engine under maximum load for an extended period of time (at least one hour).
4.The temperature difference between the two should not exceed 15 degrees F.
Note that opening any door, window or other opening can upset the
MN2408 | Receiving & Installation 3‐3 |