Operator Control and Display Panel
10.11 UPS Status Messages
The Liebert® NX™ displays status changes as they occur in the current status window of the LCD, then stores that data in the history log, as shown in Figure 61.
•Current Status Window: The status messages are displayed chronologically and include the date and time of the events. Three status messages are visible in the window at a time. To see other messages, use the navigation keys to scroll up or down the list. A status message remains in the current status area of the LCD until the status changes, when it is moved to the history log.
•History Log: When a record moves to the history log, the time the status changed is recorded. The history log can hold up to 512 records. History log records may be viewed by accessing the Records menu.
Figure 61 Current status and history log records
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Liebert NX |
| 12:30:36 |
| ||
|
|
|
|
|
|
| Single |
| Normal |
| |
|
|
|
|
|
| Battery |
| History |
| Language |
|
|
|
|
|
|
| Inverter in setting |
|
|
|
| |
|
|
|
|
|
| 12 | :21:12 |
|
|
| |
|
|
|
|
|
| 12 | :21:12 |
|
|
| |
|
|
|
|
|
| UPS shutdown |
|
|
|
|
|
|
|
|
|
|
| 12 | :21:12 |
|
|
| |
|
|
|
|
|
| 12 | :30:16 |
|
|
| |
|
|
|
|
|
| Bypass abnormal |
|
|
|
| |
|
|
|
|
|
| 12 | :21:12 |
|
|
| |
|
|
|
|
|
| 12 | :30:16 |
|
|
| |
Current |
|
|
|
|
| Input disconnect closed |
| ||||
|
|
|
|
|
| ||||||
|
|
|
| Output disconnect closed |
| ||||||
|
|
|
|
| |||||||
Status |
|
|
| Bypass disconnect open |
|
| |||||
Messages |
|
|
|
|
| ? |
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
History Log (records menu)
F1 | F2 | F3 | F4 | HELP |
See Appendix A for a complete list of status messages, along with a description and any recommended actions.