Battery Installation

4.0BATTERY INSTALLATION

4.1Introduction

If using multiple sets of batteries connected in parallel to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection.

When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Liebert® representative for a list of approved batteries.

4.2Safety

Special care should be taken when working with the batteries associated with the Liebert NXsystem equipment. When all batteries are connected together, the battery terminal voltage may exceed 480V and is POTENTIALLY LETHAL.

WARNING

Risk of electric shock. Can cause injury, property damage and death.

Special care should be taken when working with the batteries associated with this equipment. Batteries are always live. Battery terminal voltage will exceed 480VDC and is potentially lethal.

In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns.

Batteries should be installed, serviced and replaced only by properly trained and qualified service personnel trained in safe battery handling methods and who have the correct PPE (Personal Protection Equipment) and tools.

The following precautions should be observed when working with the batteries:

• Eye protection should be worn to prevent injury from electrical arcs.

• Remove rings, watches and all other metal objects.

• Use only tools with insulated handles.

• Wear rubber gloves and boots.

• When replacing batteries, replace them with the same type and number of batteries or bat- tery packs.

• Do not dispose of batteries in a fire. The batteries may explode.

• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.

• Never lay metal objects of any type on top of the batteries.

• Disconnect the charging source before connecting or disconnecting battery terminals.

• Determine whether the battery is grounded. If the battery is grounded, remove source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.

! CAUTION

Risk of explosion and fire. Can cause property damage, injury and death.

To reduce the risk of fire, connect only to a circuit provided with correct amperes maximum branch circuit overcurrent protection (see Table 12) in accordance with the National Electric Code, ANSI/NFPA 70.

NOTE

The maximum available fault current from the battery supply is 8500A and the DC voltage rating of the battery supply overcurrent protective device that is to be installed near the battery supply must be at least 600VDC.

23

Page 33
Image 33
Emerson 40-200KVA user manual Introduction, Safety