Emerson 40-200KVA user manual Battery Run Times, Enersys battery run times in minutes

Models: 40-200KVA

1 132
Download 132 pages 42.81 Kb
Page 124
Image 124

Specifications and Technical Data

13.4Battery Run Times

Table 47 Enersys battery run times in minutes

 

 

 

 

 

Softscale Range

 

 

 

 

Scalable to 80kVA

Scalable to 120kVA

Scalable to 200kVA

External Battery Cabinet

 

 

 

Rated Output, kVA

Rated Output, kVA

Rated Output, kVA

Type

Quantity

40

60

80

80

100

120

160

200

HX205FR

1

19

11

7

N/A

N/A

N/A

N/A

N/A

HX300FR

1

31

17

12

12

8

6

N/A

N/A

HX330FR

1

36

22

15

15

11

8

5

N/A

HX400RF

1

40

26

18

18

13

10

6

N/A

HX500FR

1

64

38

27

27

20

16

10

7

HX205FR

2

41

27

19

N/A

N/A

N/A

N/A

N/A

HX300FR

2

70

41

32

32

22

18

12

9

HX330FR

2

90

52

37

37

28

23

16

11

HX400RF

2

98

62

41

41

34

27

19

14

HX500FR

2

146

93

66

66

49

38

28

21

HX205FR

3

70

41

33

N/A

N/A

N/A

N/A

N/A

HX300FR

3

109

71

50

51

38

32

21

16

HX330FR

3

146

92

63

63

47

38

27

20

HX400RF

3

156

100

72

72

54

41

32

23

HX500FR

3

224

148

105

106

80

67

46

35

HX205FR

4

97

63

45

N/A

N/A

N/A

N/A

N/A

HX300FR

4

153

99

71

72

54

41

33

23

HX330FR

4

202

131

93

94

69

53

38

30

HX400RF

4

216

142

101

102

77

64

41

35

HX500FR

4

317

206

149

150

113

95

68

50

114

Page 124
Image 124
Emerson 40-200KVA user manual Battery Run Times, Enersys battery run times in minutes