Installation Drawings

8.0INSTALLATION DRAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert® NXUPS System cabinets.

Figure 25 Outline drawing, Liebert NX 40-120kVA

 

 

 

25.5 (648)

Power Cable Entry

 

 

 

 

3.7 x 22.8 (94x 580)

 

 

 

 

23.6 (600)

 

 

 

 

 

 

 

 

SIDE VIEW

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

TOP VIEW

 

 

 

 

 

Center

 

Display

 

 

 

 

78.7

of Gravity

 

33.1

Detail A

 

 

(2000)

 

 

 

Center

 

 

(842)

 

 

 

 

 

 

 

 

 

FRONT

 

 

 

 

 

 

of Gravity

 

 

 

 

 

 

 

 

 

 

 

20.3

FRONT

40.9

 

 

 

 

 

(515)

 

 

 

 

 

 

 

(1040)

 

 

 

 

 

Power Cable Entry

 

 

 

 

 

38.5 (978)

 

 

 

 

 

4.9

x 11.4 (125 x290)

 

 

 

 

 

39 (990)

 

 

 

 

 

 

 

 

 

 

15.4

 

To Display

 

 

 

 

 

(390)

 

BOTTOM VIEW

 

 

1.6 (40)

20.9

FRONT VIEW

 

 

 

 

 

 

(530)

 

 

 

 

3.7 (94) Caster

 

 

 

 

 

 

 

 

 

 

 

Outer Panel

To Outside Frame

1. All dimensions are in inches (mm).

 

 

 

1.55 (39) Leveler

2. Minimum clearance 36" front and 8" top

 

Caster

 

to Outside Frame (See Note 9)

 

1.6 (41) Leveler to Outside Frame

required for air exhaust.

 

 

 

 

 

 

 

 

3. Keep cabinet within 15 deg. of vertical

 

 

 

3.5 (90) Caster

while handling.

 

 

5.9 (150)

 

To Outside Frame

4. Top and bottom cable entry available

 

to Outside

 

 

through removable access plates.

 

 

Frame

 

 

 

 

 

 

 

Remove punch to suit conduit size and replace.

 

 

Outer Panel

5.Color: Black.

6.Unit bottom is structurally adequate for forklift

 

handling.

Power

 

 

 

 

 

1.5 (38) Cable Panel

7.

Open door to replace air filter, washable type.

Cable

 

 

 

 

 

To Outside Frame

Entry

DETAIL A

8.

Side panels are removed between adjacent units

 

 

 

 

 

 

 

 

 

 

 

 

 

that are bolted together.

9. Leveling feet are not designed to carry the full weight of the

U3819203

cabinet. Finger-tighten leveler against the floor, then tighten

Rev. 4

with a wrench less than two turns for friction fit against floor.

 

 

Table 22 Weights, Liebert NX 40-120kVA

 

 

 

 

 

 

 

 

 

 

 

UPS Weight, lb (kg)

Heat

Cooling Air

 

 

 

 

 

 

 

kVA Rating

Net

Crated

BTU/Hr

CFM

 

 

40

1290 (585

1440 (653)

11612

620

 

 

60

1290 (585

1440 (653)

15204

620

 

 

80

1290 (585

1440 (653)

20273

620

 

 

80*

1422 (645

1572 (713)

19700

920

 

 

100*

1422 (645

1572 (713)

23496

920

 

 

120

1422 (645

1572 (713)

28196

920

 

Source: U3819203, Rev. 4

51

Page 61
Image 61
Emerson 40-200KVA user manual Outline drawing, Liebert NX 40-120kVA, Weights, Liebert NX 40-120kVA