Electrical Connections
3.1.2UPS Input Configuration
Figure 3 illustrates the Liebert® NX™ in a split bypass (dual-input) configuration. In this configuration, the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally with properly sized protective devices. By default, the unit ships with internal links installed between the bypass input and main input (Single Input configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the input bus bars, then wire the main input directly to CB1 (see Figure 3).
Figure 3 Single module block diagram—dual input configuration
Internal Maintenance Bypass | ||
3W + Gnd | ||
|
Static Bypass | ||
3W + Gnd | ||
|
AC Input | Rectifier | Inverter |
|
| Converter |
| UPS Cabinet |
|
| 2W + Gnd |
|
3W + Gnd
AC Output
Battery Cabinet
3.1.3Cabling Guidelines
The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.
1.The ground conductor should be sized in accordance with the input overcurrent protection device data in Table 8. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit.
Output and input cables must be run in separate conduit.
2.Consider using paralleled smaller cables for heavy
3.When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in UPS terminal. For terminal connection sizing, see Table 8.
4.In most installations, especially parallel
NOTE
If more load is added to the distribution panel, the unit’s cabling must be resized.
5.When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference.
14