Emerson 40-200KVA user manual Liebert NX 160-200kVA dimensions-front and left side

Models: 40-200KVA

1 132
Download 132 pages 42.81 Kb
Page 64
Image 64
U3819621 Rev. 1

 

 

 

 

 

 

 

Installation Drawings

Figure 28

Liebert® NX160-200kVA dimensions—front and left side

 

 

 

 

 

39.0 (990) to Display

 

 

 

 

 

 

48.9 (1242)

38.5 (978)

 

 

 

 

 

 

 

 

 

 

 

61.9

 

 

 

 

 

 

 

 

(1573)

 

 

Power Cable

 

 

 

 

 

 

 

 

 

 

 

 

Low Voltage

 

 

Entry

 

 

 

 

 

Entry

 

14 x 13 (355x330)

 

 

 

 

 

5.1 x 3.9

 

 

 

 

 

 

 

 

(130x100)

 

 

 

 

 

 

 

 

2.7 (68)

 

 

.8 (19)

 

 

 

 

 

.9 (23)

.4 (10)

Front

 

 

 

 

78.7

Front

Outside

Outside

Frame

 

 

 

 

Frame

Frame

Frame

 

 

 

 

 

 

 

 

 

 

(2000)

 

 

 

 

 

 

 

 

 

TOP VIEW (Door Open)

 

 

 

 

 

 

 

DETAIL A

1.6 (41) Outside

 

 

 

 

 

 

 

 

Frame Typ

 

 

FRONT

RIGHT SIDE

 

 

 

1.6 (41) Outside

 

 

 

 

3

Frame Typ

 

 

5.0 (127) Typ

 

 

 

(76)

 

 

 

38.9 (987)

 

REAR

 

See Detail A

 

 

 

 

 

4.1 (104)

 

To Centers of Caster Brkt. Typ

 

 

 

 

 

 

 

 

 

5.7 (146) Typ

 

 

 

 

 

 

 

 

27.1 (688)

 

 

 

33.1

 

 

 

 

To Centers

 

 

 

 

 

 

 

of Caster

 

 

 

(842)

 

 

 

 

Brkt. Typ

 

 

 

Typ

 

 

1.9 (49)

Front

7.3 (186)

43.7 (1111) Typ.

 

 

 

Front Frame

 

 

 

32.3 x 6.4 (820x163)

LEVELER SPACING

 

 

 

 

Outside Frame

 

 

 

 

Cable Entry Panel

 

 

 

Looking Top Down

BOTTOM

(Looking Top Down)

NOTES:

1.All dimensions are in inches [mm]. Weight est. 2201 lb. (1000kg).

2.24" [610] minimum clearance above unit required for air exhaust, and 36" [914] minimum service clearance at front of unit.

3.Keep cabinet within 15 degrees of vertical.

4.Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.

5.Control wiring and power wiring must be run in separate conduits.

6.Aluminum and copper-clad aluminum cables are not recommended.

7. All wiring is to be in accordance with national and local electrical codes.

8. Depth dimensions include front door and rear panel.

9. Width dimension includes side panels. Subtract 2.2" (56mm) when removing both side panels.

Table 26 Electrical specifications, Liebert NX 160-200kVA

 

 

Voltage

Heat

 

 

 

 

 

Rejection

Cooling Air

 

 

 

 

Rating, kVA

Input

 

Output

BTU/hr

CFM

 

 

 

 

 

 

160

480

 

480

35,900

1590

 

 

 

 

 

 

200

480

 

480

47,000

1590

 

 

 

 

 

 

Source: U3819621, Rev. 1

54

Page 64
Image 64
Emerson 40-200KVA Liebert NX 160-200kVA dimensions-front and left side, Electrical specifications, Liebert NX 160-200kVA