Installation Drawings

Figure 36 Outline drawing, 33" battery power pack system, single cabinet

609.3

(24)

872.2

(34.3)

Max. Door Swing: 120°

 

896.6

169.5 (6.7)

 

(35.3)

372.7 (14.7)

172.1

26.8 (1.1)

 

 

(6.8)

 

474.3

 

322.9

 

575.9

(12.7)

 

(18.7)(22.7)

322.9

 

 

 

(12.7)

 

779.1

 

 

 

 

(30.7)

Bottom

(Viewed From Below)

Top

(Viewed From Above)

845

(33.2)

418.9 (16.5)

Center

of Gravity

2000

(78.7)

683

(26.9)

Front

(Without Door)

965

 

(38)

490.3

 

(19.3)

 

Center

 

of Gravity

Leveling Feet (See Note #9)

Right Side

1.All dimensions are in millimeters (inches)

2.Minimum clearance 36" front and 8" top required for air exhaust.

3.Top and bottom cable entry available through removable access plates.

4.Keep cabinet within 15 deg. of vertical while handling.

5.Control wiring and power wiring must be run in separate conduit.

6.Aluminum and copper clad cables are not recommended.

7.All wiring is to be in accordance with national and local electrical codes.

8.Intercabinet wiring between the UPS and the external battery cabinet is field-supplied.

9.Leveling feet are not designed to carry the full weight of the cabinet.

Finger-tight leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.

10.Side panels included.

11.M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used the weight of the unit must be supported under

all casters. Mounting holes same spacing front and rear.

13.Battery-support tray connects to the front of the cabinet with the

support brackets. Without the support, the battery may fall out of the cabinet.