Operating Instructions

11.0OPERATING INSTRUCTIONS

11.1Liebert® NXOperating Modes

The Liebert NX can operate in any of four modes, as shown in Table 32. This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations.

Table 32 UPS operating modes

 

Circuit Breaker

 

Operating Mode

State

Description

 

 

 

Normal

CB1:ON

 

CB2:ON

The UPS is powering the load.

Operation

CB3:OFF

 

 

CB5:ON

 

 

 

 

On Maintenance

CB1:OFF

The UPS is shut down but the load is connected to utility power via the

CB2:OFF

Maintenance Bypass Supply line.

Bypass

CB3:ON

NOTE: The load is not protected against disturbances in AC input power in

 

CB5:OFF

this mode.

 

CB1:ON

No load power is supplied by the UPS. The load is connected to utility power

On Test

CB2:ON

via the Maintenance Bypass Supply line.

CB3:ON

NOTE: The load is not protected against disturbances in AC input power in

 

 

CB5:OFF

this mode.

 

 

 

 

CB1:ON or OFF

The load power is supplied through the static bypass line. This may be

On Static Bypass

CB2:ON

considered as a temporary mode during load transfers between inverter and

CB3:OFF

 

CB5:ON

maintenance bypass or supply under abnormal operating conditions.

 

 

 

 

 

NOTE

1. The user controls and indicators mentioned in these procedures are identified in 10.0 - Operator Control and Display Panel.

2.The audible alarm may sound at various points during these procedures. It can be canceled at any time by pressing the SILENCE ON/OFF push button.

NOTE

This section refers to some modes and conditions that are set or adjusted using proprietary service software. To take advantage of all the available features for the Liebert NX, the unit must be commissioned by a Liebert factory-trained service engineer.