UPS Specifications
6.4.3Inverter Output
Table 13 Inverter output
Rated Power kVA | 40 | 60 |
| 80 | 100 | 120 |
| 160 | 200 | |
Rated voltage, VAC |
|
|
|
| 480 |
|
|
|
| |
Supply |
|
|
|
|
| |||||
Frequency, Hz |
|
|
| 60 (50Hz in frequency converter mode) |
|
| ||||
Rated Power, kW | 36 | 54 |
| 72 | 90 | 108 |
| 144 | 180 | |
|
|
| 105% to 110% for 60 minutes |
|
| |||||
|
|
| 111% to 125% for 10 minutes |
|
| |||||
overload, min. load |
|
|
|
|
| |||||
|
|
| 126% to 150% for 1 minute |
|
| |||||
|
|
|
|
|
| |||||
| ±1% | |||||||||
| effects of input voltage, connected load, battery voltage, ambient temperature and load | |||||||||
Voltage Regulation% | power factor |
|
|
|
|
|
|
| ||
±2% | ||||||||||
| ||||||||||
| effects of input voltage, connected load, battery voltage, ambient temperature and load | |||||||||
| power factor |
|
|
|
|
|
|
| ||
Frequency Regulation% |
| Nominal frequency regulation is ±0.05% in single module mode, |
| |||||||
|
|
| and+/- 0.25% in parallel mode. |
|
| |||||
|
|
|
|
|
| |||||
Maximum rate of change |
| Selectable from 0.1Hz/sec to 3.0Hz/sec maximum for single unit |
| |||||||
of frequency, Hz/sec |
|
| Fixed maximum of 0.2Hz/sec for paralleled units |
|
See Table 8 for current ratings.
6.4.4Bypass Input
Table 14 Bypass input
Rated Power, kVA | 40 |
| 60 |
| 80 |
| 100 |
| 120 |
| 160 | 200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated voltage, VAC |
|
|
|
|
| 480 |
|
|
|
|
| |
|
|
|
|
|
|
|
| |||||
Supply |
|
|
|
|
|
| ||||||
|
|
|
| |||||||||
Bypass voltage tolerance% | Upper limit: +10%, +15% or +20%; Upper limit default: +15% |
|
| |||||||||
Lower limit: |
| |||||||||||
|
| |||||||||||
Frequency, Hz |
|
|
|
|
| 60 |
|
|
|
|
| |
|
|
|
|
|
|
| ||||||
Input frequency tolerance% |
|
|
| ±2.5%, ±5%, ±10% and ±20%; default ±10% |
|
| ||||||
|
|
|
|
| ||||||||
|
| Rated Output Current: Duration of Overload |
|
| ||||||||
Bypass overload |
|
| 105% to 110%: | 60 Minutes |
|
|
|
| ||||
|
| 111% to 125%: | 10 Minutes |
|
|
|
| |||||
capacity (all ratings) |
|
|
|
|
|
| ||||||
|
| 126% to 150%: | 1 Minute |
|
|
|
| |||||
|
|
|
|
|
|
| ||||||
|
|
|
| 1000%: | 100 Milliseconds |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
See Table 8 for current ratings.
Bypass frequency synchronization range setting should be wider than bypass frequency shift range.
40