Image 50

UPS Specifications

6.4.3Inverter Output

Table 13 Inverter output

Rated Power kVA

40

60

 

80

100

120

 

160

200

Rated voltage, VAC

 

 

 

 

480

 

 

 

 

Supply

 

 

 

3-phase, 3-wire plus ground

 

 

Frequency, Hz

 

 

 

60 (50Hz in frequency converter mode)

 

 

Rated Power, kW

36

54

 

72

90

108

 

144

180

Three-phase transient

 

 

 

105% to 110% for 60 minutes

 

 

 

 

 

111% to 125% for 10 minutes

 

 

overload, min. load

 

 

 

 

 

 

 

 

126% to 150% for 1 minute

 

 

 

 

 

 

 

 

 

±1% 3-phase RMS average for a balanced three-phase load for the combined variation

 

effects of input voltage, connected load, battery voltage, ambient temperature and load

Voltage Regulation%

power factor

 

 

 

 

 

 

 

±2% 3-phase RMS average for a 100% unbalanced load for the combined variation

 

 

effects of input voltage, connected load, battery voltage, ambient temperature and load

 

power factor

 

 

 

 

 

 

 

Frequency Regulation%

 

Nominal frequency regulation is ±0.05% in single module mode,

 

 

 

 

and+/- 0.25% in parallel mode.

 

 

 

 

 

 

 

 

Maximum rate of change

 

Selectable from 0.1Hz/sec to 3.0Hz/sec maximum for single unit

 

of frequency, Hz/sec

 

 

Fixed maximum of 0.2Hz/sec for paralleled units

 

See Table 8 for current ratings.

6.4.4Bypass Input

Table 14 Bypass input

Rated Power, kVA

40

 

60

 

80

 

100

 

120

 

160

200

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated voltage, VAC

 

 

 

 

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

 

3-phase, 3-wire plus ground

 

 

 

 

 

 

Bypass voltage tolerance%

Upper limit: +10%, +15% or +20%; Upper limit default: +15%

 

 

Lower limit: -10%, -20%, -30% or -40%; Lower limit default: -20%

 

 

 

Frequency, Hz

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

Input frequency tolerance%

 

 

 

±2.5%, ±5%, ±10% and ±20%; default ±10%

 

 

 

 

 

 

 

 

 

Rated Output Current: Duration of Overload

 

 

Bypass overload

 

 

105% to 110%:

60 Minutes

 

 

 

 

 

 

111% to 125%:

10 Minutes

 

 

 

 

capacity (all ratings)

 

 

 

 

 

 

 

 

126% to 150%:

1 Minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000%:

100 Milliseconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Table 8 for current ratings.

Bypass frequency synchronization range setting should be wider than bypass frequency shift range.

40