Options

12.0OPTIONS

Several items of optional equipment are available for connection to the Liebert® NXUPS.

12.1Communication and Other User Terminals

The UPS can be integrated into advanced networking environments via UPS monitoring software such as Microsoft UPS Monitor, Liebert MultiLink, Liebert Nform, Liebert SiteNet, Modbus / Jbus, Liebert SiteScan, Liebert SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the server and PCs.

Figure 68 Monitoring board (U2) auxiliary terminal block detail

J8

 

 

 

J3

J1

 

 

LCD

J22

X7

 

 

 

 

 

J23

X6

 

 

J12

 

 

J2

J9

 

 

 

 

 

 

J15

PWR

 

 

MODEM

X5

 

 

SNMP CARD

 

J16

 

 

 

J17

 

Liebert IntelliSlot 2

X4

X4

 

 

J13

J21

J25

J28

J4

J26

J30

J10

BFP

INV ACF

EPO

Dry in

MBC

BCB

 

X1

 

X2

 

X3

 

 

Liebert IntelliSlot 1

Liebert IntelliSlot 3

J24

NOTE: The black square () on each slot indicates Pin 1.

12.1.1Analog Input Interface

At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 2 percent. “ENV-T” is used for environment temperature detecting.

X6 pin 1: Not used

X6 pin 2: +12V

X6 pin 3: ENV-T – environment temperature detection

X6 pin 4: GND

12.1.2Power Output

The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 12V. The maximum current is 500mA.

12.1.3Liebert IntelliSlot Communication

The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communication cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for external signaling of operating status.

The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is operating.

106

Page 116
Image 116
Emerson 40-200KVA user manual Communication and Other User Terminals, Analog Input Interface, Power Output