11.3Partially De-Energize the Liebert Nx 480 with Internal Maintenance Bypass

Follow the procedure below to transfer the load from the inverter output to the internal Maintenance Bypass line of the UPS.

NOTICE

Risk of improper operation. Can cause property damage from loss of power to connected load.

Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load.

This procedure assumes that the UPS is operating normally.

1.Press the INVERTER OFF button on the operator control panel for longer than 2 seconds.

The Inverter indicator will turn off and the status indicator will turn amber and an audible alarm will sound. The load will transfer to static bypass and the inverter will shut off.

NOTE

Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message displayed until the relevant condition is rectified.

2.Close maintenance breaker CB3.

The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply.

3.Open output breaker CB5. This ends the bypass procedure. The load is now powered directly from the Maintenance Bypass supply.

4.Press the EPO (Emergency Power Off) button at the UPS front panel of this UPS module only. This will disable further Rectifier, Inverter, Static Switch and Battery operation. This will not affect the manual maintenance bypass power switch. If a Liebert® NXbattery cabinet is connected, the battery circuit breaker will shunt trip open.

5.Open the rectifier switch CB1 and bypass breaker CB2.

All operator indicators and messages will turn off as the utility-driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual Maintenance bypass.

! WARNING

Risk of electrical shock. Can cause injury and death.

Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers.

! WARNING

Risk of electrical shock. Can cause injury and death.

Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized. Service is to be performed by qualified personnel only.

NOTICE

Risk of loss of power to connected load. Can cause property damage.

The load equipment is not protected from normal supply aberrations when operating in maintenance bypass mode.

• To return unit to normal operation, follow the steps in 11.2.1 - Startup Procedure.