UPS Status Messages
Table 49 UPS status messages
Event Message | Description / Suggested Action (if any) | |
|
| |
| This alarm is triggered by an inverter software routine when the amplitude or frequency of | |
| bypass voltage exceeds the limit. | |
| This alarm automatically resets once the bypass voltage goes normal. | |
| First check whether there are relevant alarms such as “Bypass disconnect open,” “Bypass | |
| phase reverse” and “Mains neutral lost.” If they appear, solve them first. | |
| Then verify that the bypass voltage and frequency displayed on the panel is within the bypass | |
Bypass Abnormal | limit. Note here the rated voltage and frequency are specified by “Output voltage level” and | |
| “Output frequency level” respectively. | |
| If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency | |
| presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is | |
| likely to trigger this alarm frequently, the bypass limit can be increased through the configuration | |
| software according to the customer’s agreement. | |
| Contact Liebert Services at | |
| This alarm is triggered by an inverter software routine when the inverter and bypass waveforms | |
| are misaligned by more than 6 degrees in phase. This alarm resets automatically once the | |
Inverter Asynchronous | condition clears. | |
First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first. | ||
| ||
| Verify the waveform of the bypass voltage. | |
| Contact Liebert Services at | |
Inverter Fault | This alarm indicates a fault condition exists within the inverter. | |
Contact Liebert Services at | ||
| ||
Output Voltage Abnormal | This alarm indicates the inverter voltage waveform is abnormal. | |
Contact Liebert Services at | ||
| ||
Input Current Abnormal | This alarm indicates the rectifier input current is abnormal. | |
Contact Liebert Services at | ||
| ||
| The temperature of the inverter filter inductor or inverter common mode inductor is too high to | |
| keep inverter running. | |
| This alarm is triggered by the signal from a thermostat mounted in the inverter filter inductor. | |
| The UPS would recover automatically after a 5 minute delay from the disappearance of the | |
| overtemperature signal. | |
Inv. Inductor Overtemp. | If the overtemperature condition is true then check for and verify: | |
| High ambient air temperature. | |
| Blocked cooling airway | |
| Any fan failure | |
| Prolonged inverter overload. | |
| Contact Liebert Services at | |
| The temperature of the inverter heat sink is too high to keep inverter running. | |
| This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter | |
| bridge heat sink. | |
| The UPS will recover automatically after a 5 minute delay from the disappearance of the | |
| overtemperature signal. | |
Inverter Overtemp. | If the overtemperature condition is true then check for and verify: | |
| high ambient air temperature. | |
| blocked cooling airway. | |
| any fan failure. | |
| prolonged inverter overload. | |
| Contact Liebert Services at | |
Fan Fault | At least one of the cooling fans has failed. Contact Liebert Services at | |
assistance. | ||
| ||
Inverter STS Fail | At least one of the static switches of inverter side is open or short circuit. This fault is locked until | |
power off. Contact Liebert Services for assistance at | ||
| ||
| At least one of the static switches of bypass side is open or | |
Bypass STS Fail | until power off. | |
| Contact Liebert Services at | |
Output Fuse Fail | At least one of the output fuses is open. Contact Liebert Services at | |
assistance. | ||
| ||
Control Power 2 Fail | Control Power 2 is abnormal or lost. Contact Liebert Services at | |
|
|