Specifications and Technical Data
Table 38 External cabinet dimensions, including side panels
Wide Parallel Cabinet
Unit | Width | Depth | Height |
|
|
|
|
mm (inch) | 1240 (48.8) | 965 (38) | 2000 (78.7) |
Narrow Parallel Cabinet |
|
| |
Unit | Width | Depth | Height |
|
|
|
|
mm (inch) | 845 (33.2) | 965 (38) | 2000 (78.7) |
|
|
|
|
33 in. Battery Cabinet |
|
| |
|
|
|
|
Unit | Width | Depth | Height |
|
|
|
|
mm (inch) | 845 (33.2) | 965 (38) | 2000 (78.7) |
|
|
|
|
13.3Cable size and tightening torques
Table 39 Cable size tightening torque at Liebert® NX™ 40kVA UPS terminals
| Cable Size | Torque to Tighten | |
Bus Type | (Copper Wire Only) | Terminal Bus & Lug Body | |
Main Input | 4 | 10 | |
(Single Input) | |||
|
| ||
Main Input | 4 | 10 | |
(Dual Input) | |||
|
| ||
Bypass Input | 4 | 10 | |
(Dual Input) | |||
|
| ||
Output | 3 | 10 | |
|
|
|
Table 40 Cable size tightening torque at Liebert NX 60kVA UPS terminals
| Cable Size | Torque to Tighten | |
Bus Type | (Copper Wire Only) | Terminal Bus & Lug Body | |
Main Input | 1 | 10 | |
(Single Input) | |||
|
| ||
Main Input | 1 | 10 | |
(Dual Input) | |||
|
| ||
Bypass Input | 2 | 10 | |
(Dual Input) | |||
|
| ||
Output | 2 | 10 |
Table 41 Cable size tightening torque at Liebert NX 80kVA UPS terminals
| Cable Size | Torque to Tighten | |
Bus Type | (Copper Wire Only) | Terminal Bus & Lug Body | |
Main Input | 2/0 | 10 | |
(Single Input) | |||
|
| ||
Main Input | 2/0 | 10 | |
(Dual Input) | |||
|
| ||
Bypass Input | 1/0 | 10 | |
(Dual Input) | |||
|
| ||
Output | 1/0 | 10 | |
|
|
|