Operating Instructions
After initialization, the bypass SCR closes. Because the output circuit breaker is still open, the UPS channels power through the Maintenance Bypass Supply line (CB3). The bypass indicator extinguishes, provided that the bypass is normal.
The opening display is shown in the figure at right. The UPS Mimic display indicators will be:
Indicator | State |
|
|
Rectifier indicator | Green |
|
|
Battery indicator | Red |
|
|
Bypass indicator | Off |
|
|
Inverter indicator | Off |
|
|
Output indicator | Off |
|
|
Status indicator | Off |
|
|
F1 | F2 | F3 | F4 | HELP |
•Close CB5 (CB1, CB2, CB3 and CB5 are closed).
•The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply.
•Verify that the Bypass indicator is Green, then open CB3.
The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the hardware and software ensures uninterrupted output.
3.Close external battery circuit breaker.
After the UPS detects that the battery is connected, the red battery indicator extinguishes moments after the battery charger starts operation.
The UPS Mimic display indicators will be
Indicator | State |
|
|
Rectifier indicator | Green |
|
|
Battery indicator | Off |
|
|
Bypass indicator | Green |
|
|
Inverter indicator | Off |
|
|
Output indicator | Green |
|
|
Status indicator | Amber |
|
|
4.Press the INVERTER ON control button for 2 seconds.
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the UPS will transfer from bypass to inverter, the bypass indicator will turn off and the inverter and load indicators will turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
Indicator | State |
|
|
Rectifier indicator | Green |
|
|
Battery indicator | Off |
|
|
Bypass indicator | Off |
|
|
Inverter indicator | Green |
|
|
Output indicator | Green |
|
|
Status indicator | Green |
|
|
96