UPS Status Messages

Table 49 UPS status messages

Event Message

Description / Suggested Action (if any)

 

 

Balancer Fault

Internal VDC (+) and VDC (-) offset by over 50V exceeding the inverter DC offset compensation

capacity. Inverter shuts down. Load transfers to bypass.

 

Operation Invalid

This record is registered following an incorrect operation.

 

 

Byp. Abnormal Shutdown

Both bypass and inverter voltages unavailable. Load interruption

 

 

Setting Save Error

History records not saved (Reserved)

 

 

Protocol version clash

Firmware incompatibility between monitor board and digital signal processor board

 

 

MBP-T cabinet Fan Fault

Maintenance bypass cabinet fans fault

 

 

Ext Input TX Overtemp

External input isolation transformer overtemperature

 

 

Ext Output TX Overtemp

External output isolation transformer overtemperature

 

 

Battery Room Alarm

Environment in Battery Room Needs Attention

 

 

Rec Flash Update

Rectifier firmware is being updated

 

 

Inv Flash Update

Inverter firmware is being updated

 

 

Monitor Flash Update

Monitor firmware is being updated

 

 

Input contactor fault

Input contactor fault

 

 

LBS abnormal

LBS is abnormal

 

 

DSP firmware error

The inverter firmware is not compatible with the rectifier firmware.

 

 

Fan power fail

Fan power has failed

 

 

Keyboard fault

Keyboard has a fault. Check the cable between keyboard with U2 board. Contact Liebert

Services at 800-543-2378 for assistance.

 

KVA Invalid

An invalid kVA has been configured in unit.Contact Liebert Services at 800-543-2378 for

assistance.

 

KVA updated

The capacity updating is successful.

 

 

Output ground fault

Output Line is shorted with ground

 

 

121