UPS Specifications
Table 8 | UPS terminal (continued) |
|
|
| |
|
|
|
|
|
|
Battery |
|
|
|
|
|
|
|
|
|
| Maximum |
|
|
|
|
| Recommended |
|
|
|
|
| Lug |
|
|
|
|
| (Thomas & |
|
|
|
|
| Betts Part #) |
Unit | Nominal | Maximum | OCP | Bolt | Compression |
Discharge | Discharge | Device | |||
Rating | Current | Current | Rating | Size | bolt |
40 | 82 at 480VDC | 103 at 384VDC | 125 | M8 | 54106 |
60 | 122 at 480VDC | 155 at 384VDC | 175 | M8 | 54107 |
80 | 163 at 480VDC | 206 at 384VDC | 225 | M8 | |
100 | 204 at 480VDC | 258 at 384VDC | 300 | M8 | 54157 |
120 | 244 at 480VDC | 309 at 384VDC | 350 | M8 | 54167 |
160 | 367 at 480VDC | 412 at 384VDC | 450 | M10 | 54115 |
200 | 408 at 480VDC | 515 at 400VDC | 600 | M10 | 54115 |
1.Nominal (Nom) current is based on full rated output load.
2.Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3.UPS input and bypass cables must be run in separate conduit from output cables.
4.Nominal battery voltage is shown at 2.0 volts/cell per NEC
5.OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215.
6.
7.Wiring requirements:
a.AC Input:
b.AC Output:
8.All wiring is to be in accordance with national and local electric codes.
6.4.1Input Rectifier
Table 9 Rectifier input power
Rated Power kVA |
| 40 | 60 |
| 80 |
| 100 |
| 120 |
| 160 |
| 200 | |||
Rated Voltage, VAC |
|
|
|
|
|
| 480 |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Supply |
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Input Voltage Tolerance, VAC |
|
|
|
| 480V Nominal +15%, |
|
|
| ||||||||
(without derating) |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Overload capacity of input |
|
|
|
|
| 100% Imax <I<125% Imax: 60 min |
|
|
| |||||||
current |
| 125% Imax <I<150% Imax: 10 min; >150% load, less than 200msec |
| |||||||||||||
Frequency, Hz |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Power Factor |
|
|
|
|
| > 0.99 at full load; >0.98 at half load |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||
Harmonic Current |
|
|
|
| Less than 3% at full rated UPS output load |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
See Table 8 for current ratings. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Table 10 Input voltage window with derating |
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||||||
Input Voltage Window |
| Percentage |
| Inverter Load, | Charger Load, |
|
|
|
|
| ||||||
| of Nominal |
| Percentage |
| Percentage |
|
|
|
|
|
| |||||
432VAC to 552VAC |
|
|
| 100% | 100% |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
431VAC to 384VAC |
|
|
| 100% | 30% |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
383VAC to 360VAC |
|
|
| 100% | 0% |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
359VAC to 288VAC |
|
|
| 80% | 0% |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
38