Specifications and Technical Data
13.2Cable Lengths: Floor to Connection Point Inside UPS
To help calculate the total cable length required, refer to Table 36 for the distance from the floor to selected connection points inside the Liebert® NX™. Determine the cable length required to reach the Liebert NX, then add the appropriate length from the table and adequate slack for repair and maintenance.
Table 36 Distance to connection points on the Liebert NX UPS
| Distance | |
|
|
|
| From Floor | From Top of Unit |
Connection Point on UPS | in. (mm) | in. (mm) |
Bypass AC input supply | 13 (330) | 66 (1676) |
|
|
|
UPS output AC | 13 (330) | 66 (1676) |
|
|
|
Battery power | 13 (330) | 66 (1676) |
|
|
|
Auxiliary cables: Monitor board (U2) | 67 (1702) | 11 (279) |
|
|
|
Liebert IntelliSlot Communications | 60 (1524) | 19 (483) |
|
|
|
Ground | 13 (330) | 66 (1676) |
|
|
|
Parallel Board | 70 (1780) | 11 (279) |
|
|
|
Table 37 Parallel system current table
|
|
| System I/P |
| System |
| Nominal | Output | |
System |
|
| Voltage | System Max | Input OCPCB | O/P Voltage | O/P Current | OCPCB | |
Size | Type | kVA | (VAC) | Input Current | Size (A) | (VAC) | Rating (A) | Size (A) | |
| E | 80 | 480V | 135.0 | 200 | 480V | 96.2 | 125 | |
|
|
|
|
|
|
|
| ||
| 120 | 480V | 202.5 | 300 | 480V | 144.3 | 200 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
1+1 | E1 | 80 | 480V | 135.0 | 200 | 480V | 96.2 | 125 | |
|
|
|
|
|
|
| |||
120 | 480V | 202.5 | 300 | 480V | 144.3 | 200 | |||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
| E2 | 80 | N/A | N/A | N/A | 480V | 96.2 | 125 | |
|
|
|
|
|
|
|
| ||
| 120 | N/A | N/A | N/A | 480V | 144.3 | 200 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
| E | 80 | 480V | 270.0 | 350 | 480V | 192.5 | 250 | |
|
|
|
|
|
|
|
| ||
| 120 | 480V | 405.0 | 600 | 480V | 288.7 | 400 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
2+1 | E1 | 80 | 480V | 270.0 | 350 | 480V | 192.5 | 250 | |
|
|
|
|
|
|
| |||
120 | 480V | 405.0 | 600 | 480V | 288.7 | 400 | |||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
| E2 | 80 | N/A | N/A | N/A | 480V | 192.5 | 250 | |
|
|
|
|
|
|
|
| ||
| 120 | N/A | N/A | N/A | 480V | 288.7 | 400 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
| E | 80 | 480V | 405.0 | 600 | 480V | 288.7 | 400 | |
|
|
|
|
|
|
|
| ||
| 120 | 480V | 607.5 | 800 | 480V | 433.0 | 600 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
3+1 | E1 | 80 | 480V | 405.0 | 600 | 480V | 288.7 | 400 | |
|
|
|
|
|
|
| |||
120 | 480V | 607.5 | 800 | 480V | 433.0 | 600 | |||
|
| ||||||||
|
|
|
|
|
|
|
|
| |
| E2 | 80 | N/A | N/A | N/A | 480V | 288.7 | 400 | |
|
|
|
|
|
|
|
| ||
| 120 | N/A | N/A | N/A | 480V | 433.0 | 600 | ||
|
| ||||||||
|
|
|
|
|
|
|
|
|
Type E: BB0, FB0 and KB0 configurations
Type E1: CB1, GB1, LB1 configurations;
Type E2: CB2, CB3, CB4 configurations
Use wiring rated at 75°C or greater.
111