Emerson 40-200KVA user manual Configuring Baud Rates, Liebert NX communication options, Comments

Models: 40-200KVA

1 132
Download 132 pages 42.81 Kb
Page 117
Image 117

Options

12.1.4Communication and Monitoring

Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card

This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured parameters for display through a Web browser.

Table 33 Liebert® NXcommunication options

 

 

On the UPS

Monitoring

 

 

Physical

Labeled

LCD screen,

 

 

description

ID Name

under Settings,

Devices

Baud

 

of port

of Port

controlled by:

supported

rate

Comments

 

 

 

Multiport 4

any

 

 

 

 

Relaycard-int

any

 

 

 

 

 

 

 

Top

Intellislot 2

 

 

 

Not simultaneous with

 

Liebert IntelliSlot

 

Multilink in RS232-1;

Liebert

(On Monitor

Comm 1

2400

WEB-LB

See 12.1.5 - Configuring

IntelliSlot

Board)

 

 

 

 

 

 

 

Baud Rates

 

 

 

Modbus/Jbus

2400

See 12.1.5 - Configuring

 

 

 

Baud Rates

 

 

 

 

 

 

 

 

Multiport 4

any

 

 

 

 

Relaycard-int

any

 

Middle

Intellislot 1

 

Liebert IntelliSlot

 

See 12.1.5 - Configuring

Liebert

(On Monitor

Comm 2

2400

Baud Rates

WEB-LB

Not simultaneous with

IntelliSlot

Board)

 

 

 

 

 

Multilink in RS232-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus/Jbus

2400

See 12.1.5 - Configuring

 

 

 

Baud Rates

 

 

 

 

 

 

 

 

Multiport 4

any

 

 

 

 

 

 

 

Bottom

Intellislot 3

 

Relaycard-int

any

 

 

Liebert IntelliSlot

 

See 12.1.5 - Configuring

Liebert

(On Monitor

Comm 3

2400

WEB-LB

Baud Rates

IntelliSlot

Board)

 

 

 

 

 

Modbus/Jbus

2400

See 12.1.5 - Configuring

 

 

 

Baud Rates

 

 

 

 

 

Top

 

 

 

 

Not simultaneous with Web

RS232-1

Comm 1

MultiLink Serial

9600

card in top Liebert

DB9 port

 

 

 

 

IntelliSlot.

 

 

 

 

 

Bottom

 

 

Service Software

 

Not simultaneous with Web

RS232-2

Comm 2

9600

card in middle Liebert

DB9 port

(Reserved)

 

 

 

IntelliSlot.

 

 

 

 

 

12.1.5Configuring Baud Rates

The default baud rate for Liebert IntelliSlot cards is 9600. To communicate with the

Liebert OCWEB-LB, Modbus/Jbus or the adapters to permit using Liebert MultiLink, the baud rate must be set to 2400.

To change the baud rate (refer to Table 33):

1.Use the Navigation keys directly below the LCD to highlight the Settings Screen.

2.Press F1 to move the highlight into the Data & Settings area of the LCD.

3.Use the Navigation keys to scroll down to highlight the current baud rate across from the appropriate Comm Channel.

NOTE

The Comm Channel settings are not immediately visible because of window-size constraints. Scroll down to view them on the screen.

4.Press the Enter (F4) key to select the Comm Channel to change.

5.Navigate to underline the desired baud rate (2400).

6.Press the Enter (F4) key to lock in the new baud rate.

107

Page 117
Image 117
Emerson 40-200KVA user manual Configuring Baud Rates, Liebert NX communication options, Comments, See 12.1.5 Configuring