Operation
Maintenance Mode
For maintenance or repair, the Liebert® NX™ may be operated in maintenance mode. To place the Liebert NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those conditions are met, the CB3 may be turned on and the UPS may be shut down, permitting disconnecting the batteries for maintenance.
! WARNING
Risk of electrical shock. Can cause injury and death.
The UPS input and output must be protected with external overcurrent protection devices. In maintenance mode, the input and output busbars remain energized.
NOTICE
Risk of improper operation. Can cause loss of power to the load and damage to the UPS.
The internal maintenance bypass must not be used when the UPS system is in a parallel system. Doing so can cause a backfeed that can damage the UPS and interrupt power to the load.
Parallel Redundancy Mode (System Expansion)
For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be programmed for directly paralleling while a
Frequency Converter Mode
The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 57Hz to 66Hz. In this mode, the static bypass operation is disabled and the battery becomes optional, depending on any requirement to operate in battery mode (stored energy mode).
Eco Mode
If ECO mode is selected, the
79