Operating Instructions
13.Close the CB5 Output Breaker.
14.Close the external battery breaker(s).
15.Verify the Battery Alarm LED extinguishes.
16.Open theCB3 Maintenance Bypass Breaker.
17.On the Control Panel, press the INVERTER ON button for 2 seconds.
18.Verify that the Inverter LED turns solid green, and that the unit indicates Normal Mode after about a minute.
11.7Auto Restart
When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.
The UPS will automatically restart and enable output power:
•after utility power is restored
•if “Auto Recovery after EOD Enabling” is enabled
•after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes)
During the auto recovery delay, the Liebert® NX™ will be charging its batteries to provide a safety margin for equipment shutdown if input power fails again.
If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system manually.
11.8Emergency Shutdown With EPO
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier and inverter and will stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If a Liebert NX battery cabinet is connected, the circuit breaker in the battery cabinet will shunt trip open.
If input utility power is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, open the external feeder breaker.
11.9Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature,
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the
NOTE
The rectifier will start again, and the bypass will begin to power the load. The Rectifier indicator flashes while the rectifier is starting up. When the rectifier enters the normal operation state (about 30 seconds), the rectifier indicator turns green.
2.Press the INVERTER ON button on the right side of the operator control panel for longer than 2 seconds.
NOTE
The rectifier will automatically turn on 5 minutes after the Inverter Overtemp alarm has cleared.