Electrical Connections

3.3Dry Contacts

The UPS provides input dry contacts and output dry contacts.

NOTE

When operating the Liebert® NXwith dry contacts, ESD measures must be taken or the contacts may be damaged.

3.3.1Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 6 Input dry contacts

+12V

+12V

+12V

+12V

X3

J4

J26

J30

J10

+12V

GEN

BtG

ENV

GND

+12V

AUX I

T IT

AUX 0

T 0T

F FAN

FUSE

OL

GND

FB

DRV

NOTE: The black square () on each slot indicates Pin 1.

Table 1

Input dry contacts at X3

 

 

 

Position

Name

Description

J4.1

ENV3

Battery Room Alarm (Normally Closed)

J4.2

BtG

Battery Ground Fault Detection (Normally Closed)

J4.3

GEN1,2

Generator Detection (Normally Open)

J4.4

+12V

+12V Power

1 - Must be configured using configuration software before becoming active.

2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

3.3.2Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 2 Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT1

Input transformer over temperature (N.C.)

J26.2

AUX_I

Reserved

 

 

 

J26.3

+12V

+12V Power

 

 

 

J26.4

GND

Power Ground

 

 

 

J30.1

FUSE

Reserved

 

 

 

J30.2

F_FAN

Fan Fail Alarm (N.C.)

 

 

 

J30.3

T_OT1

Output Transformer Overtemperature (N.C.)

J30.4

AUX_O

Reserved

1- Must be configured using configuration software before becoming active.

NOTE

All auxiliary cables of terminal must be double-insulated. The wire must be 600V, 18-16 AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.