Operator Control and Display Panel

 

 

 

Table 31 Descriptions of UPS menus and data window items (continued)

 

 

 

Menu Type

Item Type

Explanation

 

 

 

 

Sout (kVA)

Sout: Apparent power

System

Pout (kW)

Pout: Active power

 

 

Qout (kVAR)

Qout: Reactive power

 

 

 

 

 

Single unit, no parallel data

When configured as a single unit, UPS has only native load, no system load.

 

Battery voltage (V)

Battery bus voltage

 

Battery current (A)

Battery bus current

 

Battery temperature (°C)

Internal battery temperature °C

Battery

 

 

Remain Time Min.

Battery run time remaining.

 

Battery boost charging

Battery is boost charging.

 

Battery float charging

Battery is float charging.

 

 

 

 

Battery disconnected

Battery is not connected.

Records

(History Log)

Displays all records in the history log.

Language

(choices for text displayed)

User may select any of 12 languages for LCD text.

 

Display contrast

Adjust the LCD contrast

 

Date format set

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

 

 

 

 

Date & time

Set the date and time

 

Comm1 baud rate

Communication baud rate setting for Liebert IntelliSlot 1

 

 

 

 

Comm2 baud rate

Communication baud rate setting for Liebert IntelliSlot 2

 

 

 

 

Comm3 baud rate

Communication baud rate setting for Liebert IntelliSlot 3

 

Communication address

This setting is applicable to RS485 communication mode.

 

 

 

Settings

Communication mode

Communication Mode Setting

 

When Liebert IntelliSlot 1 Communication mode is Modem, this parameter

Settings

Callback times

sets the number of times a number is redialed to send an alarm notification.

 

 

 

 

 

 

Phone No.1

When Liebert IntelliSlot 1 Communication mode is Modem, this is the first

 

phone number to be dialed (to send an alarm notification).

 

 

 

Phone No.2

When Liebert IntelliSlot 1 Communication mode is Modem, this is the second

 

phone number to be dialed (to send an alarm notification).

 

 

 

Phone No.3

When Liebert IntelliSlot 1 Communication mode is Modem, this is the third

 

phone number to be dialed (to send an alarm notification).

 

 

 

Command password

User can modify the command password.

 

Audible Alarm

User can Enable and Disable the UPS audible alarm.

 

Battery maintenance test

This test performs a partial discharge of the battery to obtain a rough estimate

 

of the battery capacity. Load must be between 20% and 80%.

 

 

 

Battery capacity test

This test performs a full discharge of the battery to obtain a precise measure of

 

the battery capacity. Load must be between 20% and 80%.

 

 

 

System test

This is a self-test of the UPS. When the user activates this function, a pop-up

Command

window appears about 5 seconds later to show the results.

 

(start/stop

 

 

Stop testing

Manually stops a battery maintenance test, battery capacity test or system

battery &

test.

system

 

 

 

Allows a temporary Equalize charge for the batteries. This charge is

tests)

Freshening Charge

configurable for 1 to 36 hours.

 

 

 

 

 

 

Stop Freshening Charge

Manually stops a Freshening Charge.

 

 

 

 

Modem Auto-answer

Manually enable the modem’s auto-answer function.

 

enable

 

 

 

Battery Commission

Resets the UPS battery detection logic after new/fresh batteries are installed.

 

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and software

Version

display board.

 

 

UPS model

Provides UPS model information—for example, 480V-60Hz.

87