| Operator Control and Display Panel | |
|
|
| |
Table 31 Descriptions of UPS menus and data window items (continued) | |||
|
|
| |
Menu Type | Item Type | Explanation | |
|
|
| |
| Sout (kVA) | Sout: Apparent power | |
System | Pout (kW) | Pout: Active power | |
|
| ||
Qout (kVAR) | Qout: Reactive power | ||
| |||
|
|
| |
| Single unit, no parallel data | When configured as a single unit, UPS has only native load, no system load. | |
| Battery voltage (V) | Battery bus voltage | |
| Battery current (A) | Battery bus current | |
| Battery temperature (°C) | Internal battery temperature °C | |
Battery |
|
| |
Remain Time Min. | Battery run time remaining. | ||
| Battery boost charging | Battery is boost charging. | |
| Battery float charging | Battery is float charging. | |
|
|
| |
| Battery disconnected | Battery is not connected. | |
Records | (History Log) | Displays all records in the history log. | |
Language | (choices for text displayed) | User may select any of 12 languages for LCD text. | |
| Display contrast | Adjust the LCD contrast | |
| Date format set | Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D | |
|
|
| |
| Date & time | Set the date and time | |
| Comm1 baud rate | Communication baud rate setting for Liebert IntelliSlot 1 | |
|
|
| |
| Comm2 baud rate | Communication baud rate setting for Liebert IntelliSlot 2 | |
|
|
| |
| Comm3 baud rate | Communication baud rate setting for Liebert IntelliSlot 3 | |
| Communication address | This setting is applicable to RS485 communication mode. | |
|
|
| |
Settings | Communication mode | Communication Mode Setting | |
| When Liebert IntelliSlot 1 Communication mode is Modem, this parameter | ||
Settings | Callback times | ||
sets the number of times a number is redialed to send an alarm notification. | |||
|
| ||
|
|
| |
| Phone No.1 | When Liebert IntelliSlot 1 Communication mode is Modem, this is the first | |
| phone number to be dialed (to send an alarm notification). | ||
|
| ||
| Phone No.2 | When Liebert IntelliSlot 1 Communication mode is Modem, this is the second | |
| phone number to be dialed (to send an alarm notification). | ||
|
| ||
| Phone No.3 | When Liebert IntelliSlot 1 Communication mode is Modem, this is the third | |
| phone number to be dialed (to send an alarm notification). | ||
|
| ||
| Command password | User can modify the command password. | |
| Audible Alarm | User can Enable and Disable the UPS audible alarm. | |
| Battery maintenance test | This test performs a partial discharge of the battery to obtain a rough estimate | |
| of the battery capacity. Load must be between 20% and 80%. | ||
|
| ||
| Battery capacity test | This test performs a full discharge of the battery to obtain a precise measure of | |
| the battery capacity. Load must be between 20% and 80%. | ||
|
| ||
| System test | This is a | |
Command | window appears about 5 seconds later to show the results. | ||
| |||
(start/stop |
|
| |
Stop testing | Manually stops a battery maintenance test, battery capacity test or system | ||
battery & | test. | ||
system |
|
| |
| Allows a temporary Equalize charge for the batteries. This charge is | ||
tests) | Freshening Charge | ||
configurable for 1 to 36 hours. | |||
|
| ||
|
|
| |
| Stop Freshening Charge | Manually stops a Freshening Charge. | |
|
|
| |
| Modem | Manually enable the modem’s | |
| enable | ||
|
| ||
| Battery Commission | Resets the UPS battery detection logic after new/fresh batteries are installed. | |
| UPS version | Provides UPS firmware version numbers for the inverter, rectifier and software | |
Version | display board. | ||
| |||
| UPS model | Provides UPS model |
87