UPS Specifications

Table 11 Liebert-approved replacement batteries

Battery

Models

Manufacturer

Supplied

 

 

 

12HX205FR

 

 

 

12HX300FR

Enersys

 

12HX330FR

 

 

 

12HX400RF

 

 

 

12HX505FR

 

 

 

45HR2000

 

 

 

24HR3000

East Penn

 

27HR3500

 

 

 

31HR4000

 

 

 

31HR5000

 

 

 

UPS12-100MR

 

 

 

UPS12-150MR

 

 

 

UPS12-210MR

C&D

 

UPS12-300MR

 

 

 

UPS12-400MR

 

 

 

UPS12-490MR

 

 

 

UPS12-540MR

 

 

6.4.2DC Intermediate Circuit

Table 12 DC intermediate circuit

Rated Power kVA

40

 

60

80

 

100

 

120

160

 

200

Recommended number

 

Total 40 battery blocks of 12VDC (240 cells of 2VDC)

 

of lead-acid batteries

 

 

 

will be supported by UPS

 

 

 

Recommended float charge voltage

 

 

 

 

2.27VDC *

 

 

 

 

Recommended boost charge voltage

 

 

 

 

 

2.4VDC *

 

 

 

 

Recommended end of discharge voltage

 

 

 

1.67 - 1.75 VDC

 

 

 

Maximum recharge battery current, A *

14.8

 

22.2

29.6

 

37.0

 

44.4

59.2

 

74

Maximum boost charge duration, min. *

 

 

 

 

1800

 

 

 

 

 

Boost-float threshold current, A *

 

 

 

 

0.1 C default

 

 

 

 

Temperature voltage compensation, mV/°C *

From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*

Ripple voltage superimposed%

 

 

 

 

 

1

 

 

 

 

* Set by configuration software and based on usage of VLRA batteries.

See Table 8 for current ratings.