UPS Specifications
Table 11 Liebert-approved replacement batteries
Battery | Models |
Manufacturer | Supplied |
|
|
| 12HX205FR |
|
|
| 12HX300FR |
Enersys |
|
12HX330FR | |
|
|
| 12HX400RF |
|
|
| 12HX505FR |
|
|
| 45HR2000 |
|
|
| 24HR3000 |
East Penn |
|
27HR3500 | |
|
|
| 31HR4000 |
|
|
| 31HR5000 |
|
|
| |
|
|
| |
|
|
| |
C&D |
|
|
|
| |
|
|
| |
|
|
| |
|
|
6.4.2DC Intermediate Circuit
Table 12 DC intermediate circuit
Rated Power kVA | 40 |
| 60 | 80 |
| 100 |
| 120 | 160 |
| 200 |
Recommended number |
| Total 40 battery blocks of 12VDC (240 cells of 2VDC) |
| ||||||||
of |
|
|
| will be supported by UPS |
|
|
| ||||
Recommended float charge voltage |
|
|
|
| 2.27VDC * |
|
|
|
| ||
Recommended boost charge voltage |
|
|
|
|
| 2.4VDC * |
|
|
|
| |
Recommended end of discharge voltage |
|
|
| 1.67 - 1.75 VDC |
|
|
| ||||
Maximum recharge battery current, A * | 14.8 |
| 22.2 | 29.6 |
| 37.0 |
| 44.4 | 59.2 |
| 74 |
Maximum boost charge duration, min. * |
|
|
|
| 1800 |
|
|
|
|
| |
|
|
|
| 0.1 C default |
|
|
|
| |||
Temperature voltage compensation, mV/°C * | From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.* | ||||||||||
Ripple voltage superimposed% |
|
|
|
|
| ≤ 1 |
|
|
|
|
* Set by configuration software and based on usage of VLRA batteries.
See Table 8 for current ratings.
39