7.1.1Bypass Mode

When the Liebert BDC is in Bypass mode, it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the UPS inverter to the bypass source. In this mode, power will still be supplied to the UPS; however, the load is NOT protected by the UPS.

7.2Maintenance Mode

When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS.

7.3Locating the Cabinet

This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit. In either case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes.

7.4Cable Installation

7.4.1Wiring Preparation

Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Liebert BDC should be installed by a qualified / certified electrician.

WARNING

Risk of electrical shock and arc flash. Can cause property damage, injury and death.

Read this section thoroughly before attempting to install wiring to this unit. Read and comply with all warnings and cautions in this manual.

Removing the Cover Plates

Plates cover the input and output terminals on the front of the Liebert BDC. Remove these and keep the screws and plates for reinstallation.

7.4.2Power Cable Installation

Refer to Table 15 when selecting cables.

Table 15 Power cable size selection (Copper Wire Only)

Bus Type

 

Main Input

Bypass Input

 

Terminal

 

 

 

Output

Single Input

Dual Input

Dual Input

Liebert® NX40kVA UPS

4

4

4

3

Liebert NX 60kVA UPS

1

1

2

2

Liebert NX 80kVA UPS

2/0

2/0

1/0

1/0

Liebert® NX100kVA UPS

4/0

4/0

2/0

2/0

Liebert NX 120kVA UPS

250

250

4/0

4/0

Liebert NX 160kVA UPS

2-3/0

2-3/0

2-3/0

2-3/0

Liebert NX 200kVA UPS

2-4/0

2-4/0

2-4/0

2-4/0

Liebert NX 480V

225A

350A

600A

Battery Cabinet DC Input Bus

4/0AWG

400kcmi

2-350kcmil

NOTE

Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load.