Tab

Button

Function

 

 

 

Metering

Digital Input Labels

The user can enter descriptive text

 

 

(limited to 22 characters) for each

 

 

digital input. These labels are retentive.

 

 

 

Control

Trigger Demand Report

Initiates a "current report" download to

 

 

a file after prompting the user to

 

 

confirm the requested action. Report

 

 

status is indicated during the download.

 

 

When the report is complete the path to

 

 

the new file is displayed.

 

 

 

 

Block/Unblock Reclosure

Blocks or Unblocks the recloser

 

 

remotely after confirmation by the user.

 

 

Active only if the recloser function is

 

 

available in the device. Will not unblock

 

 

reclosers blocked locally.

 

 

 

 

Open/Close Breaker

Opens or closes the breaker attached to

 

 

the device after confirmation by the

 

 

user. This button is disabled if the

 

 

relay’s breaker status input is unwired.

 

 

See the relay manual for details.

 

 

 

Control

Reset Fault Log

Clears the device fault log record after

 

 

confirmation by the user.

 

 

 

 

Reset Event Log

Clears the device event log record after

 

 

confirmation by the user.

 

 

 

 

Disable Relay

Toggles the relay Enable/Disable

 

 

setpoint after confirmation by the user.

 

 

 

 

Group 1 - 6

Changes the relay’s active setpoint

 

 

group to the selected value (1 – 6) after

 

 

confirmation by the user.

 

 

 

Table 39. DFP100 Tabular data screen commands.

General notes on controls:

1.If the communications link between the device and the wizard has failed (as indicated by the "Communications failed" warning) then all Control tab command buttons will display the message "Communications Failure – please wait" in response to command requests.

2.While a warning or prompt message box is displayed by the wizard, all wizard controls such as command buttons and tab selectors are disabled.

3.A 15 second consecutive-command delay is enforced between command requests. While this delay is in progress, additional command requests will display the message "Device Busy – please wait".