Tab

Button

Function

 

 

 

Control

Lockout Recloser

If the recloser status is "In Progress" and the breaker is open, this command

 

 

forces the recloser to the Lockout state.

 

 

 

 

Reset Recloser

If the recloser status is "In Progress" and the breaker is closed, this

 

 

command forces the recloser to the Reset State.

 

 

 

 

Open/Close Breaker

Sends the "Open Breaker" or “Close Breaker” command.

 

 

 

 

Enable/Disable Digital Outputs

Toggles the status of the Digital Outputs between Enabled and Disabled.

 

 

 

 

Reset Fault Data

Clears Regular and RMS oscillography records.

 

 

 

 

Reset Latched Alarms

Resets all Latched Alarms. Use this button to clear relay front panel alarm

 

 

indicators.

 

 

 

 

Reset Event/Diag. Logs

Clears the Event and Diagnostic logs.

 

 

 

 

Reset THD Osc. Data

Clears all THD Oscillography records.

 

 

 

 

Reset Demand Data

Clears all demand values and resets all timestamps to the current time.

 

 

 

 

Reset Energy Meter Data

Zeros energy metering values for Watt-hours and Var-hours.

 

 

 

 

Group 1 – Group 8

Selects the active settings group. If the "Remote Configuration" jumper is

 

 

installed, attempts to operate these controls will generate the error message

 

 

"Remote Setpoint Changes Not Allowed: Unable to Perform Operation".

 

 

 

I/O

Digital Input and Output Labels

The user may replace the existing labels for each I/O point. These labels are

 

 

retentive.

 

 

 

Table 40. DFP200 Tabular data screen commands.

Notes on Control Tab:

1.Attempts to operate command buttons during DDE communication failure will generate the error message "Communications Failure: please wait".

2.All command buttons, tab selectors, and function buttons are disabled until wizard message boxes are acknowledged.

Notes on breaker controls: the following configuration options will affect the operation of the breaker command controls:

1.If the "Remote Breaker Operations Disabled" jumper is installed on the relay, attempts to issue Breaker Open and Breaker Close commands will generate the error message "Remote Breaker Operations Not Allowed – Unable to Perform Operation".

3.If the Digital Outputs are Disabled, attempts to issue Breaker Open and Breaker Close commands will generate the error message "Digital Outputs Disabled: Unable to Perform Operation".

PMCS Interface Toolkit

Features of Tabular Data Screen Wizards 189

Page 195
Image 195
GE DEH-210 manual DFP200 Tabular data screen commands