Circuit Breaker One-Line Wizards

After placing a Horizontal or Vertical Circuit Breaker wizard in a window, double- click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

Enter text to display next to the breaker graphic during runtime (optional).

Enter the name of the discrete tag that determines the color of the line to the left (or bottom) of the breaker symbol during runtime.

Enter the name of the discrete tag that determines the color of the line to the right (or top) of the breaker symbol during runtime.

Enter the name of the analog tag that determines the color of the circuit breaker symbol, the state of the breaker, and the status text displayed next to the breaker icon during runtime.

Specify the colors of the wizard elements and status text for the breaker states during runtime. See the table below for default status/ color mappings.

The breaker status values and the associated default colors are listed in the table below. Error status indicates that the breaker status inputs create an indeterminate state for the breaker.

Breaker Status

Value

Text

Default Color

 

 

 

 

Open

1

OPN

Green

 

 

 

 

Closed

3

CLD

Red

 

 

 

 

Drawn Out

5

OUT

Green

 

 

 

 

Tripped

7

TRP

Yellow

 

 

 

 

Error

9

ERR

Flashing Red

 

 

 

 

Breaker status values & display colors.

PMCS Interface Toolkit

Configuring and Using PMCS Wizards 39

Page 45
Image 45
GE DEH-210 manual Circuit Breaker One-Line Wizards, Breaker Status Value Text Default Color