Power Quality Meter (PQM)
The PQM's large faceplate wizard provides the following animated functions:
Feature | Function |
|
|
Meter Display | Opens the tabular data window specified during wizard |
| configuration and sets the view to the Metering tab. |
|
|
Setpoint button | Opens the tabular data window specified during wizard |
| configuration and sets the view to the Setpoints tab. |
|
|
Reset button | Opens the tabular data window specified during wizard |
| configuration and sets the view to the Metering tab, which offers a |
| button to issue a RESET command to the device. |
|
|
Actual button | Pressing the ACTUAL button rotates through the three Main |
| Actual Value pages on the device: A1 Metering, A2 Status, and A3 |
| Product Info. If the ACTUAL button is pressed while the display |
| shows a subgroup or a line, the display will jump back to the Page |
| header. |
|
|
Message | Scrolls forward/backward through the subgroups for the currently |
Up/Down buttons | selected page. |
|
|
Message | Scrolls through individual lines for each subgroup within a page. |
Right/Left | For most lines, an actual value and units from the device are |
buttons | displayed. |
|
|
Panel Display | Display animation that shows the status of the PQM relay. |
Lights |
|
|
|
Table 8. PQM Faceplate animated functions.
NOTE: The PQM Large Faceplate Wizard cannot display values greater than 2 to the 31st power. Therefore, numbers greater than 231 (unscaled) for Energy and Apparent Energy may appear negative. The values affected are kWh, kvarh, kVAh, Energy Cost and kVA. The Tabular Data Screen wizard show the correct values.
78 ∙ Features of GE Large Faceplate Wizards | PMCS Interface Toolkit |