EPM 3720 Meter

The EPM 3720 Tabular Data Screen wizard has several special features. You can use the Setup 1, Setup 2, and Setpoints screens to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others provide scroll buttons, and some have both.

The Download and Refresh buttons on the Setup 1 and Setup 2 screens upload and download the values for all of the setup parameters.

The Download and Refresh buttons on the Setpoints screen upload and download all of the setpoints from the device.

The Reset Energy Integrators and Reset All Min/Max buttons on the Setup 1 screen provide the named functions.

The Sliding Demand tab supports downloading of up to 10 sliding demand measurements to the device. See Appendix B for information on setting the sliding demand keys.

To change setpoints at the device, first press the Refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the Download button to send all setpoints to unit.

When you first open the EPM 3720 Tabular Data Screen, you may see values of zero in all fields. The EPM 3720 Tabular Data Screen requires some user interaction (such as pressing a key) to update its values.

PMCS Interface Toolkit

Features of Tabular Data Screen Wizards 125

Page 131
Image 131
GE DEH-210 manual EPM 3720 Meter