Feature

Function

 

 

STORE Button

Resets the meter at two special points in the display of values.

 

Press STORE to toggle the response on the bottom line.

 

 

PAGE Buttons

Rotate among seven pages of parameter data. Press one of the

 

arrow keys to display PAGE #: ACTUAL VALUES on the top

 

line, a description on the bottom, and reset to the first parameter

 

value. The seven pages are listed in the following tables.

 

 

LINE Buttons

Rotate among parameters within a page. Certain configurations

 

or meter values may prevent display of all parameters within a

 

page. The parameters in each page are listed in the table below.

 

 

Panel Display Lights

Display animation that shows the status of the 269 Plus relay. If a trip or alarm has occurred, auxiliary relay 1 or 2 is active. If the meter fails its self-test, the dark red square to the left of the label appears bright red.

Table 14. 269+ Faceplate animated functions.

The following table lists the pages that can be accessed with the PAGE buttons, with the parameters available in each page that can be accessed with the LINE buttons.

Page

Value

Text Displayed

Description

 

 

 

 

 

1

PAGE 1: ACTUAL VALUES

Page header

 

 

PHASE CURRENT DATA

 

 

 

 

 

 

 

2

I1=xxx

I2=xxx

Phase current in amps; --- or RUN based on

 

 

I3=xxx

(AMPS)---

motor status

 

 

 

 

 

 

3

I(3 Ph avg.)=xxx

AMPS

Average phase current

 

 

Max Stator RTD=xxx C

Hottest stator temperature

 

 

 

 

1

4

UNBALANCE RATIO (In/Ip)

 

 

 

U/B=xx

PERCENT

 

 

 

 

 

 

5

GROUND FAULT CURRENT

Units = *.1 if G/F CT

 

 

G/F=xxx.0

 

AMPS

ratio = 2000:1

 

 

 

 

 

6

ST/HR TIMERS (MIN)

Starts per hour

 

 

xx xx xx xx xx

 

 

 

 

 

 

 

7

TIME BETWEEN STARTS

 

 

 

TIMER = xxx

MIN

 

 

 

 

 

 

8

END OF PAGE ONE

Page footer

 

 

ACTUAL VALUES

 

 

 

 

 

 

1

PAGE 2: ACTUAL VALUES

Page header

 

 

RTD TEMPERATURE DATA

 

 

 

 

 

 

2

HOTTEST STATOR RTD

 

 

 

RTD #xx = xxx

 

 

 

 

 

 

 

3-12

RTD TEMPERATURE

Displays temperatures of RTDs #1-10

 

 

RTD # xx = xxx

 

 

 

 

 

 

2

13

MAX STATOR SINCE LAST

 

 

 

ACCESS: RTD #x = xxx DEGREES C

 

 

 

 

 

 

14-17

MAXIMUM RTD #x TEMP SINCE

Displays #7-10 max

 

 

LAST ACCESS: xxx DEGREES C

 

 

 

 

 

 

18

CLEAR LAST ACCESS DATA?

Press STORE to clear; message changes to

 

 

NO

 

 

YES

 

 

 

 

 

19

END OF PAGE TWO

Page footer

 

 

ACTUAL VALUES

 

92 Features of GE Large Faceplate Wizards

PMCS Interface Toolkit

Page 98
Image 98
GE DEH-210 manual Value Text Displayed Description