The action keys specify the instance number for an object to perform an action on.

 

 

The following action keys are possible:

 

 

 

 

Action Key

Setpoint

 

Meaning

 

Supported

 

 

0

-

 

No action

 

 

 

 

1000-1004

STD HS

 

Clear digital input counter 0-3 (Status input counter 1-4), 4=ALL

 

 

 

 

1100-1102

STD HS

 

Operate Relay #1 to 3

 

 

 

 

1C00-1C04

STD HS

 

same as 1000-1004

 

 

 

 

A400-A407

STD HS

 

Waveform Capture channels #1 to 8

 

 

 

 

A500

STD HS

 

Waveform Recorder

 

 

 

 

Action keys marked with STD are supported by Standard Setpoints (1–11), action keys marked with HS are supported by High Speed Setpoints (1–6).