{set the bus status for the incoming feeds to the dependent bus below in the

distribution hierarchy. The IF_THEN

statements in this section traverse the hierarchy from top to bottom, left to right, and then bottom to top, right to left.} bus6 = 0;

bus7 = 0;

{two main feeds }

IF (bus1 AND brk1_s) THEN bus3 = 1;

ENDIF;

IF (bus2 AND brk2_s) THEN bus4 = 1;

ENDIF;

{left to right across tie breaker } IF (bus3 AND brk3_s) THEN

bus4 = 1;

ENDIF;

IF (bus4 AND brk4_s) THEN bus5 = 1;

ENDIF;

{two outgoing feeders }

IF (bus3 AND brk5_s) THEN bus6 = 1;

ENDIF;

IF (bus5 AND brk6_s) THEN bus7 = 1;

ENDIF;

{back feed from two outgoing feeds } IF (bus7 AND brk6_s) THEN

bus5 = 1;

ENDIF;

IF (bus6 AND brk5_s) THEN bus3 = 1;

ENDIF;

{right to left across tie breaker } IF (bus5 AND brk4_s) THEN

bus4 = 1;

ENDIF;

IF (bus4 AND brk3_s) THEN bus3 = 1;

ENDIF;

{two incoming feeds }

IF (bus5 AND brk2_s) THEN bus2 = 1;

ENDIF;

IF (bus3 AND brk1_s) THEN bus1 = 1;

ENDIF;

60

PMCS Interface Toolkit

Page 68
Image 68
GE GEH-6513, EPM5200P, EPM9450Q, EPM 7300, EPM 7700, PMCS 6.11a, EPM9650Q manual Endif