Multi-Speed Select ~Binary Operation

 

 

 

 

 

 

 

 

The inverter can store up to 16 different target

Multi-

 

 

 

 

 

 

frequencies (speeds) that the motor output uses for

speed

 

CF4

CF3

CF2

CF1

 

steady-state run condition. These speeds are accessible

Speed 0

 

through programming four of the intelligent terminals as

0

0

0

0

 

Speed 1

0

0

0

1

 

binary-encoded inputs CF1 to CF4 per the table to the

 

Speed 2

0

0

1

0

 

right. These can be any of the six inputs, and in any

Speed 3

0

0

1

1

 

order. You can use fewer inputs if you need eight or

Speed 4

0

1

0

0

 

fewer speeds.

 

Speed 5

0

1

0

1

 

 

 

 

Speed 6

0

1

1

0

 

NOTE: When choosing a subset of speeds to use,

Speed 7

0

1

1

1

 

Speed 8

1

0

0

0

 

always start at the top of the table, and

with the

Speed 9

1

0

0

1

 

least-significant bit: CF1, CF2, etc.

 

Speed 10

1

0

1

0

 

 

 

 

Speed 11

1

0

1

1

 

3rd

Speed

 

Speed 12

1

1

0

0

 

 

 

Speed 13

1

1

0

1

 

7th

 

 

 

 

 

Speed 14

1

1

1

0

 

5th

 

 

 

2nd

 

 

Speed 15

1

1

1

1

 

1st

 

 

 

 

 

 

 

 

 

6th

 

The example with eight speeds in the

 

4th

 

 

0th

 

figure below shows how input switches

[CF1]

1

 

configured for CF1–CF3 functions can

 

change the motor speed in real time.

0

 

[CF2]

1

 

 

 

 

 

 

 

 

0

 

NOTE:

Speed

0

depends

on

 

 

 

A001

[CF3]

1

 

0

 

parameter value.

 

 

 

 

 

[FW]

1

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option Terminal Code Symbol

Function Name

State

Description

02

CF1

Multi-speed Select,

ON

Binary encoded speed select, Bit 0, logical 1

 

 

 

 

Bit 0

(LSB)

OFF

Binary encoded speed select, Bit 0, logical 0

03

CF2

Multi-speed Select,

ON

Binary encoded speed select, Bit 1, logical 1

 

 

 

 

Bit 1

 

OFF

Binary encoded speed select, Bit 1, logical 0

04

CF3

Multi-speed Select,

ON

Binary encoded speed select, Bit 2, logical 1

 

 

 

 

Bit 2

 

OFF

Binary encoded speed select, Bit 2, logical 0

05

CF4

Multi-speed Select,

ON

Binary encoded speed select, Bit 3, logical 1

 

 

 

 

Bit 3

(MSB)

OFF

Binary encoded speed select, Bit 3, logical 0

 

 

 

 

C001

C007

 

Example (some CF inputs require input

 

 

 

 

~

 

configuration; some are default inputs):

 

Required settings

 

F001, A001=02,

 

 

 

A020 to A035

 

 

 

 

 

 

 

 

 

 

 

 

 

CF4 CF3 CF2 CF1

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

7 6 5 4 3 2 1 L PLC P24

 

When programming the multi-speed settings, be

 

sure to press the SET key each time and then set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the next multi-speed setting. Note that when the

 

 

 

 

 

 

 

 

key is not pressed, no data will be set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When a multi-speed setting more than 50Hz (60Hz) is to be set, it is necessary to program the

maximum frequency A004 high enough to allow

See I/O specs on page 21,22.

that speed

 

32

Page 34
Image 34
Hitachi hitachi series inverter user manual Multi-Speed Select ~Binary Operation, Required settings