Run

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Name

 

 

 

Description

 

 

 

 

Mode

 

 

 

Initialdata

 

 

 

Units

 

 

Code

 

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C076

 

Communication error

 

 

 

Selects inverter response to

 

 

 

 

 

 

 

 

02

 

 

 

 

 

 

 

select

 

 

 

communications error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Five options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Decelerate to a stop and trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Free run stop (coasting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04Decelerates to a stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C077

 

Communication error

 

 

 

Sets the communications watchdog

 

 

 

 

 

 

 

 

0.00

 

 

 

sec.

 

 

 

 

time-out

 

 

 

timer period.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 99.99 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0 = disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C078

 

Communication wait time

 

 

 

Time the inverter waits after

 

 

 

 

 

 

 

 

0.

 

 

msec.

 

 

 

 

 

 

 

 

receiving a message before it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0. to 1000. ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C081

 

O input span calibration

 

 

 

Scale factor between the external

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

 

 

 

 

frequency command on terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L–O (voltage input) and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency output,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C082

 

OI input span calibration

 

 

Scale factor between the external

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

 

 

 

 

frequency command on terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L–OI (voltage input) and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency output,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C085

 

Thermistor input (PTC)

 

 

 

Scale factor of PTC input.

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

span calibration

 

 

 

Range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C091

 

Debug mode enable

 

 

 

Displays debug parameters.

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enable <Do not set>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(for factory use)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C096

 

Communication selection

 

 

 

00Modbus-RTU

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

01EzCOM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02EzCOM<administrator>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C098

 

EzCOM start adr. of master

 

01-08

 

 

 

 

 

 

 

 

01

 

 

 

C099

 

EzCOM end adr. of master

 

01-08

 

 

 

 

 

 

 

 

01

 

 

 

C100

 

EzCOM starting trigger

 

 

 

00Input terminal

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

01Always

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C101

 

Up/Down memory mode

 

 

 

Controls speed setpoint for the

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

selection

 

 

 

inverter after power cycle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Clear last frequency (return to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

default frequency F001)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Keep last frequency adjusted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by UP/DWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69

Page 71
Image 71