78
Motor Constants Functions
“H” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
H001 Auto-tuning selection Three option codes:
00Disabled
01Enabled with motor stop
02Enabled with motor rotation
U 00 -

H002 Motor constant selection U 00 -

H202 Motor constant selection,
2nd motor
Two option codes:
00Hitachi standard motor
02Auto tuned data
U 00 -

H003 Motor capacity U kW

H203 Motor capacity,
2nd motor
Twelve selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5 U
Specified by
the capacity of
each inverter
model kW

H004 Motor poles setting U 4 poles

H204 Motor poles setting,
2nd motor
Five selections:
2 / 4 / 6 / 8 / 10
U 4 poles
H005 Motor speed response
constant 100. -
H205 Motor speed response
constant, 2nd motor
Set range is 1 to 1000
100. -

H006 Motor stabilization constant 100.

H206 Motor stabilization
constant, 2nd motor
Motor constant (factory set),
range is 0 to 255
100.
H020 Motor constant R1
(Hitachi motor) U Ohm
H220 Motor constant R1,
2
nd
motor (Hitachi motor)
0.001~65.535 ohms
U Ohm
H021 Motor constant R2
(Hitachi motor) U Ohm
H221 Motor constant R2,
2
nd
motor
(Hitachi motor)
0.001~65.535 ohms
U Ohm
H022 Motor constant L
(Hitachi motor) U mH
H222 Motor constant L,
2
nd
motor
(Hitachi motor)
0.01~655.35mH
U mH
H023 Motor constant I0
(Hitachi motor) U A
H223 Motor constant I0,
2
nd
motor
(Hitachi motor)
0.01~655.35A
U A
H024 Motor constant J
(Hitachi motor) U kgm2
H224 Motor constant J,
2
nd
motor
(Hitachi motor)
0.001~9999 kgm2
U
Specified by
the capacity of
each inverter
mode
kgm2
H030 Motor constant R1
(Auto tuned data) U ohm
H230 Motor constant R1,
2
nd
motor
(Auto tuned data)
0.001~65.535 ohms
U ohm
H031 Motor constant R2
(Auto tuned data)
0.001~65.535 ohms U
Specified by
the capacity of
each inverter
mode
ohm