Reset Inverter
The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The alarm output will be cleared within 30 ms after the onset of the Reset command.
|
| 12 ms |
[RS] | 1 | minimum |
| ||
| 0 |
|
|
| Approx. 30 ms |
Alarm | 1 |
|
signal | 0 | t |
|
|
WARNING: After the Reset command is given and the alarm reset occurs, the motor will restart suddenly if the Run command is already active. Be sure to set the alarm reset after verifying that the Run command is OFF to prevent injury to personnel.
Option Terminal Code Symbol
Function Name
State
Description
18 | RS | Reset Inverter |
| ON | The motor output is turned OFF, the Trip Mode is | ||||||||||||||||||
|
|
|
|
|
| cleared (if it exists), and powerup reset is applied | |||||||||||||||||
|
|
|
|
| OFF | Normal power ON operation | |||||||||||||||||
|
|
| C001 C007 |
| Example (default input configuration shown see | ||||||||||||||||||
|
|
| ~ |
|
| page 66): | |||||||||||||||||
|
|
| (none) |
| |||||||||||||||||||
| Notes: |
|
|
|
|
|
| RS | |||||||||||||||
| • While the control terminal [RS] input is ON, the |
| 7 | 6 | 5 | 4 | 3 | 2 | 1 | L | PLC | P24 |
| ||||||||||
| keypad displays alternating segments. After RS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| turns OFF, the display recovers automatically. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| • Pressing the Stop/Reset key of the digital operator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| can generate a reset operation only when an |
| See I/O specs on page 21,22. | ||||||||||||||||||||
| alarm occurs. |
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•A terminal configured with the [RS] function can only be configured for normally open operation. The terminal cannot be used in the normally closed contact state.
•When input power is turned ON, the inverter performs the same reset operation as it does when a pulse on the [RS] terminal occurs.
•The Stop/Reset key on the inverter is only operational for a few seconds after inverter powerup when a
•If the [RS] terminal is turned ON while the motor is running, the motor will be free running (coasting).
•If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS] terminal affects the
35