Run

 

 

 

 

Func.

Name

 

Description

Mode

 

Initialdata

 

Units

Code

 

 

 

Edit

 

 

 

 

B133

Decel. overvolt. suppress

 

Proportional gain when b130=01.

 

 

0.20

 

 

proportional gain

 

Range is: 0.00 to 5.00

 

 

 

 

 

B134

Decel. overvolt. suppress

 

Integration time when b130=01.

 

 

1.0

 

sec

 

integral time

 

Range is: 0.00 to 150.0

 

 

 

 

 

b145

GS input mode

 

Two option codes:

 

 

00

 

-

 

 

 

00No trip (Hardware shutoff only)

 

 

 

 

 

 

 

 

01Trip

 

 

 

 

 

b150

Display ex.operator connected

 

When an external operator is

 

 

001

 

 

 

 

connected via RS-422 port, the

 

 

 

 

 

 

 

 

built-in display is locked and shows

 

 

 

 

 

 

 

 

only one "d" parameter configured

 

 

 

 

 

 

 

 

in:

 

 

 

 

 

 

 

 

d001 ~ d030

 

 

 

 

 

b160

1st parameter of Dual Monitor

 

Set any two "d" parameters in b160

 

 

001

 

 

 

 

and b161, then they can be

 

 

 

 

 

 

 

 

monitored in d050. The two

 

 

 

 

 

 

 

 

parameters are switched by

 

 

 

 

 

 

 

 

up/down keys.

 

 

 

 

 

 

 

 

Set range: d001 ~ d030

 

 

 

 

 

b161

2nd parameter of Dual Monitor

 

 

 

 

002

 

 

 

 

 

 

 

 

 

 

b163

Frequency set in monitoring

 

Two option codes:

 

 

00

 

-

 

 

 

00Freq. set disabled

 

 

 

 

 

 

 

 

01Freq. set enabled

 

 

 

 

 

b164

Automatic return to the initial

 

10 min. after the last key operation,

 

 

00

 

-

 

display

 

display returns to the initial

 

 

 

 

 

 

 

 

parameter set by b038. Two option

 

 

 

 

 

 

 

 

codes:

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

01Enable

 

 

 

 

 

b165

Ex. operator com. loss action

 

Five option codes:

 

 

02

 

-

 

 

 

00Trip

 

 

 

 

 

 

 

 

01Trip after deceleration to a stop

 

 

 

 

 

 

 

 

02Ignore

 

 

 

 

 

 

 

 

03Coasting (FRS)

 

 

 

 

 

 

 

 

04Decelerates to a stop

 

 

 

 

 

b166

Data Read/Write select

 

00Read/Write OK

 

 

00

 

-

 

 

 

01Protected

 

 

 

 

 

b171

Inverter mode selection

 

Three option codes:

 

 

00

 

-

 

 

 

00No function

 

 

 

 

 

 

 

 

01Std. IM (Induction Motor)

 

 

 

 

 

 

 

 

03PM (Permanent Magnet Motor)

 

 

 

 

 

b180

Initialization trigger

 

This is to perform initialization by

 

 

00

 

-

 

(*)

 

parameter input with b084, b085 and

 

 

 

 

 

 

 

 

b094. Two option codes:

 

 

 

 

 

 

 

 

00Initialization disable

 

 

 

 

 

 

 

 

01Perform initialization

 

 

 

 

 

b190

Password Settings A

 

0000(Invalid Password)

 

 

0000

 

-

 

 

 

0001-FFFF(Password)

 

 

 

 

 

b191

Password authentication A

 

0000-FFFF

 

 

0000

 

-

 

 

 

 

 

 

 

 

 

b192

Password Settings B

 

0000(Invalid Password)

 

 

0000

 

-

 

 

 

0001-FFFF(Password)

 

 

 

 

 

b193

Password authentication B

 

0000-FFFF

 

 

0000

 

-

 

 

 

 

 

 

 

 

 

65

Page 67
Image 67
Hitachi hitachi series inverter B133, B134, B145, B150, B160, B161, B163, B164, B165, B166, B171, B180, B190, B191, B192