68
“C” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
C047 Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
1.00
C052 PID FBV output
high limit
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
U 100.0 %
C053 PID FBV output
low limit
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U 0.0 %
C054 Over-torque/under-torque
selection
Two option codes:
00Over-torque
01Under-torque
U 00 -
C055 Over/under-torque level
(Forward powering mode)
Set range is 0 to 200% U 100. %
C056 Over/under-torque level
(Reverse regen. mode)
Set range is 0 to 200% U 100. %
C057 Over/under-torque level
(Reverse powering mode)
Set range is 0 to 200% U 100. %
C058 Over/under-torque level
(Forward regen. mode)
Set range is 0 to 200% U 100. %
C059 Signal output mode of
Over/under-torque
Two option codes:
00During accel., decel. and
constant speed
01During constant speed only
U 01 -
C061 Electronic thermal warning
level
Set range is 0 to 100%
Setting 0 means disabled.
U 90 %

C063 Zero speed detection level Set range is 0.0 to 100.0Hz U 0.00 Hz

C064 Heat sink overheat warning Set range is 0 to 110 °C U 100. °C

C071 Communication speed Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
U 05 baud
C072 Modbus address Set the addr ess of the inverter on
the network. Range is 1 to 247
U 1.
C074 Communication parity Three option codes:
00No parity
01Even parity
02Odd parity
U 00
C075 Communication stop bit Two option codes:
11 bit
22 bit
U 1 bit