66
Intelligent Terminal Functions “C” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
C001 Input [1] function Select input terminal [1] function,
68 options (see next section)
U 00 [FW]
−
C002 Input [2] function Select input terminal [2] function,
68 options (see next section) U 01
[RV]
−
C003 Input [3] function
[GS1 assignable]
Select input terminal [3] function,
68 options (see next section)
U 02 [CF1]
−
C004 Input [4] function
[GS2 assignable]
Select input terminal [4] function,
68 options (see next section) U 03
[CF2]
−
C005 Input [5] function
[PTC assignable]
Select input terminal [5] function,
68 options (see next section) U 09
[2CH]
−
C006 Input [6] function Select input terminal [6] function,
68 options (see next section)
U 18 [RS]
−
C007 Input [7] function Select input terminal [7] function,
68 options (see next section) U 13
[USP]
−
C011 Input [1] active state U 00 −
C012 Input [2] active state U 00 −
C013 Input [3] active state U 00 −
C014 Input [4] active state U 00 −
C015 Input [5] active state U 00 −
C016 Input [6] active state U 00 −
C017 Input [7] active state
Select logic conversion, two option
codes:
00…normally open [NO]
01…normally closed [NC]
U 00 − C021 Output [11] function
[EDM assignable] U 01
[FA1]
−
C022 Output [12] function
48 programmable functions
available for logic (discrete) outputs
(see next section) U 00
[RUN]
−
C026 Alarm relay function 48 programmable functions
available for logic (discrete) outputs
(see next section)
U 05 [AL]
−
C027 [EO] terminal selection
(Pulse/PWM output)
13 programmable functions:
00…Output frequency (PWM)
01…Output current (PWM)
02…Output torque (PWM)
03…Output frequency (Pulse train)
04…Output voltage (PWM)
05…Input power (PWM)
06…Electronic thermal load ratio
(PWM)
07…LAD frequency (PWM)
08…Output current (Pulse train)
10…Heat sink temperature (PWM)
12…General output (PWM)
15…Pulse train input monitor
16…Option(PWM)
U 07 −