60
“b” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
b025 Overload restriction level 2 Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting
resolution is 1% of rated current
U Rated current
x 1.5
b026 Deceleration rate 2 at overload
restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
U 1.0 sec. b027 OC suppression selection Two option codes:
00…Disabled
01…Enabled
U 01 −
B028 Current level of active freq.
matching
Sets the current level of active freq.
matching restart, range is
0.1*inverter rated current to
2.0*inverter rated current, resolution
0.1
U Rated current
A
B029 Deceleration rate of active
freq. matching
Sets the deceleration rate when
active freq. matching restart, range
is 0.1 to 3000.0, resolution 0.1
U 0.5 sec. B030 Start freq. of active freq.
matching
Three option codes:
00…freq at previous shutoff
01…start from max. Hz
02…start from set frequency
U 00 −
B031 Software lock mode selection Prevents parameter changes, in five
options, option codes:
00…all parameters except B031 are
locked when [SFT] terminal is
ON
01…all parameters except B031 and
output frequency F001 are
locked when [SFT] terminal is
ON
02…all parameters except B031 are
locked
03…all parameters except B031 and
output frequency F001 are
locked
10…High level access including
B031
See appendix C for the accessible
parameters in this mode.
U 01 −
B033 Motor cable length parameter Set range is 5 to 20. U 10. −
b034 Run/power ON warning time Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
U 0. Hrs.
B035 Rotation direction restriction Three option codes:
00…No restriction
01…Reverse rotation is restricted
02…Forward rotation is restricted
U 00 −
b036 Reduced voltage start
selection
Set range, 0 (disabling the function),
1 (approx. 6ms) to 255 (approx.
1.5s)
U 2 −