83
“P” Function Defaults
Func.
Code Name Description
Run
Mode
Edit Initial data Units
P072 Position range (Forward) 0 to +268435455(Higher 4-digits
displayed) +2684354
55
Pulse
s
P073 Position range (Reverse) –268435455 to 0(Higher 4-digits
displayed) -2684354
55
Pulse
s
P075 Positioning mode selection 00…With limitation
01…No limitation (shorter route)
P004 is to be set 00 or 01
U 00
-
P077 Encoder disconnection
timeout 0.0 to 10.0 s 1.0 s
p100
~
P131
EzSQ user parameter
U(00) ~ U(31)
Each set range is 0~65535
0. -
P140 EzCOM number of data 1 to 5 5 -
P141 EzCOM destination 1 adderss 1 to 247 1 -
P142 EzCOM destination 1 register 0000 to FFFF 0000 -
P143 EzCOM source 1 register 0000 to FFFF 0000 -
P144 EzCOM destination 2 adderss 1 to 247 2 -
P145 EzCOM destination 2 register 0000 to FFFF 0000 -
P146 EzCOM source 2 register 0000 to FFFF 0000 -
P147 EzCOM destination 3 adderss 1 to 247 3 -
P148 EzCOM destination 3 register 0000 to FFFF 0000 -
P149 EzCOM source 3 register 0000 to FFFF 0000 -
P150 EzCOM destination 4 adderss 1 to 247 4 -
P151 EzCOM destination 4 register 0000 to FFFF 0000 -
P152 EzCOM source 4 register 0000 to FFFF 0000 -
P153 EzCOM destination 5 adderss 1 to 247 5 -
P154 EzCOM destination 5 register 0000 to FFFF 0000 -
P155 EzCOM source 5 register 0000 to FFFF 0000 -