Error

 

 

Name

 

 

Cause(s)

 

 

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E25

 

 

Main circuit

 

 

The inverter will trip if the power supply establishment is

 

 

 

 

 

 

error (*3)

 

 

not recognized because of a malfunction due to noise or

 

 

 

 

 

 

 

 

 

damage to the main circuit element.

 

 

 

E30

 

 

Driver error

 

 

An internal inverter error has occurred at the safety

 

 

 

 

 

 

 

 

 

protection circuit between the CPU and main driver unit.

 

 

 

 

 

 

 

 

 

Excessive electrical noise may be the cause. The inverter

 

 

 

 

 

 

 

 

 

has turned OFF the IGBT module output.

 

 

 

E35

 

 

Thermistor

 

When a thermistor is connected to terminals [5] and [L]

 

 

 

 

 

 

 

 

 

and the inverter has sensed the temperature is too high,

 

 

 

 

 

 

 

 

 

the inverter trips and turns OFF the output.

 

 

 

E36

 

 

Braking error

 

When "01" has been specified for the Brake Control

 

 

 

 

 

 

 

 

 

Enable (b120), the inverter will trip if it cannot receive the

 

 

 

 

 

 

 

 

 

braking confirmation signal within the

 

 

 

 

 

 

 

 

 

Brake Wait Time for Confirmation (b124) after the output

 

 

 

 

 

 

 

 

 

of the brake release signal.

 

 

 

E37

 

 

Safe Stop

 

 

Safe stop signal is given.

 

 

 

E38

 

 

Low-speed overload protection

 

If overload occurs during the motor operation at a very low

 

 

 

 

 

 

 

 

 

speed, the inverter will detect the

 

 

 

 

 

 

 

 

 

overload and shut off the inverter output.

 

 

 

E40

 

 

Operator connection

 

When the connection between inverter and operator

 

 

 

 

 

 

 

 

 

keypad failed, inverter trips and displays the error code.

 

 

 

E41

 

 

Modbus communication error

 

 

When “trip” is selected (C076=00) as a behavior in case of

 

 

 

 

 

 

 

 

 

communication error, inverter trips when timeout happens.

 

 

 

E43

 

 

EzSQ invalid instruction

 

The program stored in inverter memory has been

 

 

 

 

 

 

 

 

 

destroyed, or the PRG terminal was turned on without a

 

 

 

 

 

 

 

 

 

program downloaded to the inverter.

 

 

 

E44

 

 

EzSQ nesting count error

 

 

Subroutines, if-statement, or for-next loop are nested in

 

 

 

 

 

 

 

 

 

more than eight layers

 

 

 

E45

 

 

EzSQ instruction error

 

 

Inverter found the command which cannot be executed.

 

 

 

E50

 

 

EzSQ user trip (0 to 9)

 

When user –defined trip happens, inverter trips and

 

 

 

to

 

 

 

 

 

displays the error code.

 

 

 

 

 

 

 

 

 

 

 

 

 

E59

 

 

 

 

 

 

 

 

 

 

E60

 

 

Option error (DeviceNet

 

 

If the disconnection due to the Bus-Off signal or timeout

 

 

 

 

 

 

Communications error)

 

 

occurs during the operation using DeviceNet commands,

 

 

 

 

 

 

 

 

 

the inverter will shut off its output and display the error

 

 

 

 

 

 

 

 

 

code shown on the right.

 

 

 

 

 

 

 

 

 

(The inverter will trip according to the settings of "P045"

 

 

 

 

 

 

 

 

 

and "P048".)

 

 

 

E61

 

 

Option error (duplicated MACID)

 

 

If two or more devices having the same

 

 

 

 

 

 

 

 

 

MAC ID are detected in the same network, the inverter will

 

 

 

 

 

 

 

 

 

display the error code shown on the right.

 

 

 

E62

 

 

Option error (External trip)

 

 

If the Force Fault/Trip bit of Attribute 17 in the Instance 1

 

 

 

 

 

 

 

 

 

of the Control Supervisory object is set to "1", the inverter

 

 

 

 

 

 

 

 

 

will shut off its output and display the error code shown on

 

 

 

 

 

 

 

 

 

the right.

 

 

 

E63

 

 

Option error

 

 

The inverter detects errors in the option board mounted in

 

 

 

to

 

 

 

 

 

the optional slot. For details, refer to the instruction

 

 

 

 

 

 

 

 

manual for the mounted option board.

 

 

 

E68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E69

 

 

Option error (inverter communication

 

 

If timeout occurs during the communication between the

 

 

 

 

 

 

error)

 

 

inverter and DeviceNet option board, the inverter will shut

 

 

 

 

 

 

 

 

 

off its output and display the error code shown on the

 

 

 

 

 

 

 

 

 

right.

 

 

 

E80

 

 

Encoder

 

 

If the encoder wiring is disconnected, an encoder

 

 

 

 

 

 

disconnection

 

 

connection error is detected, the encoder fails, or an

 

 

 

 

 

 

 

 

 

encoder that does not support line driver output is used,

 

 

 

 

 

 

 

 

 

the inverter will shut off its output and display the error

 

 

 

 

 

 

 

 

 

code shown on the right.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 